Subheader; Data Length Setting - Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual

Ethernet
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

■Subheader

The RJ71EN71 or the RnENCPU (network part) automatically adds and deletes the subheader, the setting is not required.
Data Format
Binary code
ASCII code

■Data length setting

Shows the amount of data in the text (command) section.
• When exchanging data with binary codes: Maximum 5113 words
• When exchanging data with ASCII codes Maximum 2556 words
Command (external device  RJ71EN71 or
RnENCPU (network part))
⋅⋅⋅
b7
b7
0
1
1
0
0
0
0
60H 00H
Subheader
⋅⋅⋅
b7
b7
0
1
1
0
0
0
"6"
6H
"0"
36H 30H 30H 30H
Subheader
Response (RJ71EN71 or RnENCPU (network
part)  external device)
b0
b0
b7
b7
0
1
1
b0
b0
b7
b7
0
0
1
1
0H
0H
0H
"E"
1.5 Communications Using the Fixed Buffer
⋅⋅⋅
b0
b0
1
0
0
0
0
0
E0H
Subheader
⋅⋅⋅
b0
b0
1
0
0
0
0
0
EH
"0"
0H
45H
30H
Subheader
1 FUNCTIONS