Protocol Detailed Setting - Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual

Ethernet
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

■Protocol Detailed Setting

Set the protocol send/receive parameters.
"Protocol Setting" window  Select a protocol  [Edit]  [Protocol Detailed Setting]
Item
Connected Device
*1
Information
Protocol Setting
*1
Information
Receive Setting
Send Setting
*1 The setting cannot be changed if the protocol was selected from the predefined protocol library.
Send/receive parameters can be set for multiple protocols by clicking the [Communication Parameter Batch
Setting] button and setting the range of the set protocol numbers, receive settings, and send settings.
1 FUNCTIONS
36
1.3 Communications Using the Predefined Protocol
Description
Manufacturer
Set the protocol maker name.
Type
Set the protocol device type.
Model
Set the protocol model.
Version
Set the protocol device version.
Description
Set a description of the protocol device.
Protocol No.
The protocol number for the selected protocol is displayed.
Protocol Name
Set the protocol name.
Communication Type
Set the protocol communication type.
Receive Wait Time
Set the time for wait after the module enters the receive data wait state.
If communication with the external device is disabled because of a disconnection and matching packet
data is not received within the specified time, the module judges that an error has occurred and cancels
the receive data wait state.
Standby Time
Set the time to wait from when the protocol set for the module enters the execution state to when the
data is actually sent. The time for the external device to enter the receive enable state can be adjusted
with this in respect to the module's send timing.