Address
Decimal
Hexadecimal
108 to 110
6CH to 6EH
116
74H
200
C8H
201
C9H
202
CAH
203
CBH
398 to 399
18EH to 18FH
20486
5006H
20487
5007H
20595
5073H
20600
5078H
Name
MELSEC-Q series Ethernet interface module
Own station MAC address
Initial value: 0H
Auto-open UDP port number
Initial value: 0H
LED status
INIT. LED (b0)
0: Off
1: On (initial processing completed)
OPEN LED (b1)
0: Off
1: On (connection open processing completed)
ERR. LED (b3)
0: Off
1: On (setting error)
COM.ERR. LED (b4)
0: Off
1: On (communication error)
Hub connection status area
Communication mode (b9)
0: Half-duplex
1: Full-duplex
Hub connection status (b10)
0: Hub not connected/disconnected
1: Hub connected
Data transmission speed (b15, b14)
00: Operating at 10BASE-T
01: Operating at 100BASE-TX
Switch status (Operational mode setting)
0: Online
1: Offline
2: Self-loopback test
3: Hardware test
Status of settings with a programming tool
Initial value: 0H
Communication data code setting (b1)
0: Communications in a binary code
1: Communications in an ASCII code
Initial/open method setting (b2)
0: No parameter setting (startup according to the sequence
program)
1: Parameter setting (startup according to the parameters)
TCP existence confirmation setting (b4)
0: Use the Ping
1: Use the KeepAlive
Send frame setting (b5)
0: Ethernet
1: IEEE 802.3
Setting of write enable/disable at RUN time (b6)
0: Disable
1: Enable
Initial timing setting (b8)
0: Do not wait for OPEN (Communications impossible at
STOP time)
1: Always wait for OPEN (Communication possible at
STOP time)
Simultaneous transmission error detection count
Remote password status
Initial value: 0H
Remote password status
Initial value: 0H
Connection No.1 Accumulated count of unlock process
abnormal end
Connection No.2 Accumulated count of unlock process
abnormal end
RJ71EN71
Own station MAC address
Initial value: MAC address of the RJ71EN71
Auto-open UDP port number
Initial value: 1388H
LED status
P ERR LED (b0)
0: Off
1: On or flashing
Hub connection status area
Communication mode (b9)
0: Half-duplex
1: Full-duplex
Hub connection status (b10)
0: Hub not connected/disconnected
1: Hub connected
Data transmission speed (b15, b14)
00: Operating at 10BASE-T
01: Operating at 100BASE-TX
10: Operating at 1000BASE-T
Module operation mode setting
0: Online mode
1: Offline mode
4: Module communication test mode
Status of settings with a programming tool
Initial value: 100H
Communication data code setting (b1)
0: Communications in a binary code
1: Communications in an ASCII code
Send frame setting (b5)
0: Ethernet (fixed)
Setting of write enable/disable at RUN time (b6)
0: Disable
1: Enable
Opening method (b8)
0: Open by program
1: Do not open by program
Receive buffer full count
Remote password lock/unlocked status (user connection)
Initial value: Depending on the remote password setting
Remote password lock/unlocked status (system
connection)
Initial value: Depending on the remote password setting
Connection No.1 Remote password mismatch count
Connection No.2 Remote password mismatch count