Error
Error details and causes
code
C1A2H
• A response to the request could not be received.
• In transient transmission, the number of relay to other
networks exceeded seven.
C1A4H
• Any of the specified command, subcommand, or
request destination module I/O number of the SLMP
message is incorrect.
• The specified clear function set by the ERRCLEAR
instruction is incorrect.
• The specified information to be read set by the ERRRD
instruction is incorrect.
• The Ethernet diagnostics, CC-Link IE Field Network
diagnostics, or CC-Link IE Controller Network
diagnostics was tried to be used when the engineering
tool is directly connected to the Ethernet port of the
RJ71EN71.
• The function which is not supported by the target
device was executed.
C1A5H
The specified target station or clear target is incorrect.
C1A6H
The specified connection number is incorrect.
C1A7H
The specified network number is incorrect.
C1A8H
The specified station number is incorrect.
C1A9H
The specified device number is incorrect.
C1AAH
The specified device name is incorrect.
C1ACH
The specified number of resends is incorrect.
C1ADH
The specified data length is incorrect.
C1AFH
The specified port number is incorrect.
C1B0H
The open processing of the specified connection has
been already completed.
C1B1H
The open processing of the specified connection has not
been completed.
C1B2H
The open or close processing using CONOPEN/
CONCLOSE/OPEN/CLOSE instruction is being executed
in the specified connection.
C1B3H
Another send or receive instruction is being executed in
the specified channel.
C1B4H
The specified arrival monitoring time is incorrect.
C1B8H
The RECV instruction was executed for the channel that
had not received data.
C1B9H
The CONOPEN/OPEN instruction cannot be executed
for the specified connection.
C1BAH
The dedicated instruction was executed with the
initialization not completed.
C1BBH
The target station CPU type of the link dedicated
instruction is incorrect.
C1BCH
The target network number of the link dedicated
instruction is incorrect.
3 TROUBLESHOOTING
318
3.5 List of Error Codes
Action
• Check and correct the response waiting time.
• Change the system configuration so that the number of
relay stations may be seven or less.
• For the RECV instruction, execute again after
correcting the channels used by own station in the
control data.
• For the RECV instruction, check that 'RECV execution
request' (Un\G5301 b0 to b7) are on.
• Check the operation of the external device.
• Check if the external device supports the executed
function.
• Check that all of the specified command,
subcommand, and request destination module I/O
number of the SLMP message is correct.
• Correct the specified value for the clear function set by
the ERRCLEAR instruction.
• Correct the specified value for the information to be
read set by the ERRRD instruction.
• Connect it directly to the CPU module (built-in Ethernet
port part) or use a USB cable to use the Ethernet
diagnostics, CC-Link IE Field Network diagnostics, or
CC-Link IE Controller Network diagnostics.
Correct the specified the target station or clear target.
Correct the setting value of the connection number.
Correct the specified network number.
Correct the specified station number.
Correct the specified device number.
Correct the specified device name.
Correct the number of resends.
Correct the specified data length.
Correct the specified port number
• Do not perform the open processing to a connection
already opened.
• When communications with the external device cannot
be performed, perform the close processing before the
open processing.
After completion of the open processing, perform the
communication.
Execute again after the CONOPEN/CONCLOSE/OPEN/
CLOSE instruction is completed.
• Change the channel number.
• Execute again after the send or receive instruction is
completed.
Set the arrival monitoring time to a value within the
allowable range.
• Correct the execution condition of the RECV
instruction for the channel that had received data.
• Correct the specified channel of the RECV instruction.
Correct the specified connection.
Execute the dedicated instruction after the initial
processing is completed.
Correct the specified target station CPU type.
• Execute the link dedicated instruction again after
correcting the network number.
• When specifying another network station, check if the
settings in "Routing Setting" of "CPU Parameter" are
made correctly.
Detailed information