Omron SYSMAC CS Series Operation Manual page 257

Loop control boards, process-control cpu units, loop controller, loop-control cpu units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Errors and Alarm Troubleshooting
LED Indicators
LED
on front of
Indicator
Loop
on front of
Controller
CPU Unit
RDY
EXEC
ERR/ALM
(See note.)
Not lit
Not lit
Flashing
(A42404,
the Incom-
patible CPU
Unit Error
Flag, is
ON.)
Not lit
Not lit
Lit
(A42401,
the Inner
Board Bus
Error Flag,
is ON.)
Problem
Cause
Incompati-
• The CS1W-LCB01/
ble CPU
05 Loop Control
Unit
Board is not mounted
under one of the fol-
lowing CPU Units:
CS1G-CPU@@H
CS1H-CPU@@H
• The Process-control
CPU Unit (CS1D-
CPU@@P) Loop
Controller is not
mounted under a
CS1D-CPU@@H
CPU Unit.
All the EM banks have
been converted into file
memory.
Inner
An Inner Board Bus
Board Bus
Error has occurred.
Error
Status
Error
code
(Stored
in error
log.)
Operation is
None
stopped.
Operation is
None
stopped.
Section 7-1
Corrective action
Replace the CPU Unit with
one of the compatible models.
Change the setting so that the
EM banks are not converted
into file memory.
Mount the Loop Control Board
securely. Replace the Loop
Control Board if the error
recurs after the Board is
secured and power is turned
ON again. If the error occurs
with the Loop Controller com-
ponent of a Loop-control CPU
Unit, replace the entire Loop-
control CPU Unit.
225