Omron SYSMAC CS Series Operation Manual page 149

Loop control boards, process-control cpu units, loop controller, loop-control cpu units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Description of Operation
Procedure
Creating a Function Block
Data File (Output to
Memory Card)
Writing Function Block
Data Files Using FINS
Commands
Set the DIP switch on the front of the CPU Unit as shown in the following
table, and then press the Memory Card Power Supply Switch for 3 s.
DIP switch on front of CPU Unit
Pin 7
ON
Loop Controller
Function
block data
flash memory
The function block file will be created and written to the Memory Card along
with the other backup files. For details, refer to 3-2-6 Simple Backup of Func-
tion Block Data to a Memory Card (LCB01/03/05 Ver. 3.0 or Later).
Note
Use an OMRON Memory Card for the Memory Card. Operation may not be
dependable if a non-OMRON Memory Card (i.e., flash memory) is used.
• The BACKIPE1.PRM file made in advance can be written to the Loop
Controller by using a FINS command (2203).
• It is not necessary to use the DIP switch or Memory Card Power Supply
Switch on the front panel of the CPU Unit.
• If a FINS command (2203) is sent while the Loop Controller is operating,
Loop Controller operation will stop.
• CPU Unit operation will continue.
• LCB operation will stop.
Pin 8
OFF
Memory Card power supply switch
CPU Unit
All data
Back up
Section 3-2
Memory Card
117