Reference: Operations At Power On - Omron SYSMAC CS Series Operation Manual

Loop control boards, process-control cpu units, loop controller, loop-control cpu units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Description of Operation
Power interruption
starts
Power interruption time where operation definitely
continues: Less than (10+T) ms
Power interruption time where operation may or may
not continue: Between (10+T) ms and (25+T) ms
Power interruption time
10+ power interruption detection extension
time of less than 10 ms
* For AC power supplies
3-2-2

Reference: Operations at Power ON

Conditions
RAM
Flash
memory
Normal
Normal
Error
Normal
(Including
data loss due
to discharged
backup
capacitor)
10 ms
Power interruption detec-
tion extension time T ms
Power interruption time where operation definitely stops: (25+T) ms or more
Power interruption detec-
tion extension time
E.g., 10 ms
Power interruption time
between (10+ power interruption detection extension time 10) ms
and (25 + power interruption detection extension time 10) ms
Power interruption
35 ms or more (25 + power interruption detection extension time 10 ms or more)
A42410
A42411
System
Common
(RAM
(Inner
Block
Error
Board
ITEM018
Flag)
Fatal
(START
Error
mode at
Flag)
Power ON)
OFF
OFF
1
(Hot start
setting)
2
(Cold start
setting)
ON
OFF
1 or 2 (Set-
ting is irrele-
vant.)
(10 + T) ms
25 ms
Power interruption detec-
tion extension time T ms
Operation may or may not continue if
power restored in this time range.
Operation
continues.
Power interruption detec-
tion extension time
E.g., 10 ms
Operation may or may not continue if
power restored in this time range.
Start method
Transfer processing
Hot start
None
Cold start
Transfers (recovers) flash
memory data to RAM and
transfers the reception
data and send/receive
data for the HMI to RAM.
Automatic Cold
Transfers (recovers) flash
start
memory data to RAM and
transfers the reception
data and send/receive
data for the HMI to RAM.
Section 3-2
(25 + T) ms
Time
Operation may or
may not continue.
Operation stops.
A35807
(Automatic
Cold Start
Execution
Flag)
OFF
OFF
ON
99