Exchanging Data with the CPU Unit
3-3-2

Commands from the CPU Unit to the Loop Controller

Auxiliary Area Control Bits Relevant to the Loop Controller
Control Bits (CPU Unit to Loop Controller)
Word Bit
Name
A608 00
Inner Board
Restart Bit
A609 01
Start Mode at
Power ON:
Hot Start
(Cannot be
used for Pro-
cess-control
CPU Unit
(CS1D-
CPU@@P).)
02
Start Mode at
Power ON:
Cold Start
(Cannot be
used for Pro-
cess-control
CPU Unit
(CS1D-
CPU@@P).)
144
The Loop Controller's start mode at power ON can be specified from the CPU
Unit.
Explanation
Turn this bit from OFF to ON to restart
the Loop Controller. (The Loop Con-
troller will start initialization.)
Note: The bit will be reset to 0 (OFF)
automatically when initialization is
completed.
When this bit is set to 1 (ON), the
Loop Controller's "start mode at power
ON" will be hot start mode (as a com-
mand from the CPU Unit to the Loop
Controller.)
This bit is effective only when
ITEM018 of the System Control block
(block model 000) is set to 3 (com-
mand from CPU Unit.)
Note: If bits A60901 and A60902 are
both ON at the same time, this bit
takes precedence and a hot start will
be performed.
When this bit is set to 1 (ON), the
Loop Controller's "start mode at power
ON" will be cold start mode (as a com-
mand from the CPU Unit to the Loop
Controller.)
This bit is effective only when
ITEM018 of the System Control block
(block model 000) is set to 3 (com-
mand from CPU Unit.)
Note: If bits A60901 and A60902 are
both ON at the same time, A60901
takes precedence and a hot start will
be performed.
Note
When ITEM018 (Start Mode at Power ON) of the System Control block (block
model 000) has been set to "3: Command from CPU Unit," the Loop Controller
will not operate (including exchanging data with the CPU Unit) until the RDY
LED indicator goes ON and either A60901 or A60902 is set to 1 (ON).
Settings
Status
when
Run
Mode
Changes
0 → 1: Restarts the
Pre-
Inner Board
served
1: Perform a hot
Pre-
start when power is
served
turned ON.
0: If A60902 is also
set to 0, the Board
stops running.
If A60902 is set to 1,
a cold start will be
performed when
power is turned ON.
1: Perform a cold
Pre-
start when power is
served
turned ON.
0: If A60901 is also
set to 0, the Board
stops running.
If A60902 is set to 1,
a hot start will be
performed when
power is turned ON.
Section 3-3