Testing PROFIBUS
A.2.4
Checking the Optical Signal Quality with PROFIBUS OLM V3
The receive level of the two optical channels can be detected using a normal
commercially available voltmeter attached to measurement sockets on the
PROFIBUS OLM V3. The voltmeter can be inserted and removed during operation
using 2 mm laboratory test plugs (see Figure A-6).
Figure A-6
This allows the following:
S The incoming optical power can be documented, for example for later
measurements (aging, damage)
S A good/bad check can be made (limit value).
The correlation between the measured output voltage and the signal quality is in
the form of a curve (see Figure A-7).