Plugging The Bus Connector Into The Module - Siemens SIMATIC NET PROFIBUS Owner's Manual

Siemens network system owner manual
Table of Contents

Advertisement

Passive Components for RS-485 Networks
4.6

Plugging the Bus Connector into the Module

Fitting the Bus Connector
To fit the bus connector, follow the steps outlined below:
1. Plug the bus connector into the module.
2. Screw the bus connector to the module.
3. If the bus connector is located at the start or end of a segment, you must
activate the terminating resistor (switch setting ON") (see Figure 4-26).
It is not possible to activate the terminating resistor on the bus connector
6ES7 972-0BA30-0XA0.
Note
Remember the following:
Terminating
resistor activated
Figure 4-26
Removing the Bus Connector
If the LAN cable is connected through, you can remove the bus connector from
the PROFIBUS-DP interface at any time without interrupting data traffic on the
bus.
4-46
S By activating the terminating resistor, the outgoing LAN cable is
disconnected from the incoming LAN cable.
S Stations equipped with a terminating resistor must always be
supplied with voltage when the network starts up and during
operation.
on
off
Bus Connector (6ES7 972-0B.11-...): Terminating Resistor Activated and
deactivated
Terminating resistor
on
not activated
off
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000