Cable Lengths For Plastic And Pcf Fo Paths - Siemens SIMATIC NET PROFIBUS Owner's Manual

Siemens network system owner manual
Table of Contents

Advertisement

3.2.3

Cable Lengths for Plastic and PCF FO Paths

The length of the transmission path on fiber-optic cables is not dependent on the
transmission rate.
Each node on the optical PROFIBUS network has repeater functionality so that the
following distance information relates to the distance between two adjacent,
interconnected PROFIBUS nodes.
The maximum cable length between two PROFIBUS nodes depends on the type
of fiber-optic cable used and the optical network components.
Table 3-7
Fiber-optic cable
SIMATIC NET
PROFIBUS
Plastic fiber-optic,
duplex cord
Plastic fiber-optic,
standard cable
PCF fiber-optic,
standard cable
Table 3-8
Fiber-optic cable
SIMATIC NET
PROFIBUS
Plastic fiber-optic,
duplex cord
Plastic fiber-optic,
standard cable
PCF fiber-optic,
standard cable
Note
S Optical buses can contain max. 32 integrated optical interfaces in series.
S Several buses of up to 32 integrated optical interfaces can only be linked
via OBTs (optical repeaters).
S In optical networks (bus, star, ring) containing only OLMs, the number of
OLMs is limited to 122.
S The number of all optical components (integrated interfaces, OBTs,
OLMs) in the optical PROFIBUS network must be specified in the
configuration tool as the "Number of OLM, OBT" parameter (see Section
3.3). This number must not exceed 122.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Permitted Cable Lengths with Integrated Optical Interfaces or OBT
Maximum cable
lengths between two
nodes (in m)
Permitted Cable Lengths in an OLM Network
Maximum cable
lengths between two
nodes (in m)
Configuring Networks
For 1 Network (= 32
nodes) (in m)
50
50
300
For 1 Network (= 32
nodes) (in m)
50
80
400
1550
1550
9300
1550
2480
12400
3-17