Segments For Transmission Rates Up To A Maximum Of - Siemens SIMATIC NET PROFIBUS Owner's Manual

Siemens network system owner manual
Table of Contents

Advertisement

Configuring Networks
3.1.3

Segments for Transmission Rates up to a Maximum of

12 Mbps
Transmission Rate up to a Maximum of 12 Mbps
Table 3-6
Possible Segment Lengths
– FC Standard Cable
Transmission Rate
– FC Robust Cable
in Mbps
– FC FRNC Cable
– FC Food Cable
– FC Underground Cable
– SIENOPYR–FR Marine Cable
3
6
12
When planning segments for transmission rates from 3 Mbps to a maximum of 12
Mbps, the following factors must be taken into account:
S To attach DTEs to bus segments, only the bus connectors permitted for 12
Mbps or the BT12M bus terminal can be used.
S The maximum length of a segment must not exceed 100 m.
S The maximum number of bus attachments (nodes, OLMs, RS-485 repeaters,...)
in one segment is restricted to 32.
S To attach a programming device or PC via a tap line, only the "SIMATIC S5/S7
connecting cable, 12 Mbps, order no. 6ES7901-4BD00-0XA0" can be used.
Note
If several bus connectors are used at electrically short distances (in other words,
the cable length between adjacent connectors is less than 1 m) (for example,
several slaves in one cubicle), avoid disconnecting several bus connectors at the
same time for longer periods. Disconnecting more than one bus connector does
not necessarily mean errors but may well reduce the reliability (immunity to noise)
of a segment.
3-8
Segment Length for Cable Type
100 m
100 m
100 m
– FC Trailing Cable
– PROFIBUS Flexible Cable
– PROFIBUS Festoon Cable
100 m
100 m
100 m
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents