Daikin REYQ-TA Series Service Manual page 92

Heat recovery 60 hz
Table of Contents

Advertisement

Protection Control
Radiation fin temperature control
Perform the following control of integrated as well as multi units for each inverter compressor.
Condition
A
B
C
Condition
A
B
C
79
Normal operation
A
Reduce compressor capacity
Fin temperature standby
REYQ72TAYDU
M1C
> 96°C (204.8°F)
> 98°C (208.4°F)
< 93°C (199.4°F)
< 95°C (203°F)
> 100°C (212°F)
> 105°C (221°F)
REYQ72TATJU
M1C
> 85°C (185°F)
> 83°C (181.4°F)
< 82°C (179.6°F)
< 80°C (176°F)
> 90°C (194°F)
> 87°C (188.6°F)
B
C
When occurring 4 times within 60
minutes, the error code L4 is output.
REYQ96-120TAYDU
M1C
M2C
> 98°C (208.4°F)
< 95°C (203°F)
> 105°C (221°F)
REYQ96-120TATJU
M1C
M2C
> 83°C (181.4°F)
< 80°C (176°F)
> 87°C (188.6°F)
SiUS371614E
REYQ144-168TAYDU
M1C
> 98°C (208.4°F)
> 82°C (179.6°F)
< 95°C (203°F)
< 79°C (174.2°F)
> 105°C (221°F)
> 86°C (186.8°F)
REYQ144-168TATJU
M1C
> 83°C (181.4°F)
> 83°C (181.4°F)
< 80°C (176°F)
< 80°C (176°F)
> 87°C (188.6°F)
> 87°C (188.6°F)
Functions and Control
M2C
M2C