Daikin REYQ-TA Series Service Manual page 87

Heat recovery 60 hz
Table of Contents

Advertisement

SiUS371614E
Heating
Pc
>
3.31 MPa
(480 psi)
9-step down
After 10
seconds
Current step
maintained
Pc
<
3.22 MPa
(467 psi)
3-step up
High pressure standby
(2 times within 40 minutes)
Functions and Control
Normal Operation
Pc
>
3.39 MPa
(492 psi)
Pc
>
3.31 MPa
(480 psi)
After 15
seconds
Pc
>
3.72 MPa
(540 psi)
Pc
<
3.17 MPa
(460 psi)
All units
Compressor step: 1
High pressure switch (4.0 MPa
(580 psi)
) is activated
Abnormal stop
(E3 is displayed)
Protection Control
Pc: High pressure sensor
detection value for master
unit
74