SiUS371614E
6.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
HTdi > 115˚C
(239˚F)
After 30 seconds
3-step down
HTdi > 115˚C
(239˚F)
After 30
seconds
9-step down
HTdi > 120˚C
(248˚F)
HTdi > 125˚C
(257˚F)
21-step down
After 30 seconds
HTdi > 130˚C
HTdi > 135˚C (275˚F)
OR
HTdi > 120˚C (248˚F)
continues for 10 minutes
Discharge pipe temperature
(2 times within 100 minutes)
Functions and Control
Upper limit compressor step:
max (Max. Step)
Normal Operation
After 20 seconds
Current
step
maintained
After 20 seconds
After 20 seconds
(266˚F)
Compressor step: 1
standby
9-step up
HTdi < 105˚C
(221˚F)
HTdi < 110˚C
(230˚F)
3-step up
Discharge pipe temperature standby
(3 times within 100 minutes)
Abnormal stop
(F3 is displayed)
Protection Control
HTdi: Value of inverter compressor
discharge pipe temperature
(Tdi) compensated with
outdoor air temperature
76