Troubleshooting by Error Code

3.19 Combination Error between Indoor Unit PCB and Fan PCB

C6
Error Code
Applicable
FXMQ-PB
Models
Method of Error
Check the condition of transmission with fan PCB (A2P) using indoor unit main PCB (A1P).
Detection
Error Decision
When the communication data of fan PCB (A2P) is determined as incorrect.
Conditions
Supposed
Causes
Troubleshooting
197
Defective fan PCB (A2P)
Defective connection of capacity setting adaptor
Field setting error
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Does
the fan PCB
part No. match that
of the spare
parts list?
YES
Was
indoor unit
main PCB (A1P)
replaced with a
spare PCB?
YES
Was
correct
capacity setting
adaptor installed
when replacing it
with a spare
PCB?
YES
NO
NO
NO
Replace it with correct fan PCB
(A2P).
After establishing transmission
for indoor and outdoor units,
diagnose the operation again.
Install correct capacity setting
adaptor.
After establishing transmission
for indoor and outdoor units,
diagnose the operation again.
Service Diagnosis
SiUS371614E