Startup Control

4. Startup Control

This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
To avoid stresses to the compressor due to oil return or else after the startup, the following control is made and
the position of the four way valve is also determined. Start both the master and the slave units simultaneously to
position the four way valve.
4.1

Startup Control in Cooling

Inverter compressor 1
(M1C)
Inverter compressor 2
(M2C)
∗ REYQ96-168TA only
Electronic expansion
valve (main)
(Y1E)
Inverter fan
M1F: REYQ72TA
M1F + M2F: REYQ96-168TA
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
Ta : Outdoor air temperature
Te : Low pressure equivalent saturation temperature
61
Frequency step up
5 sec. interval
E
D
C
B
A
0 Hz
0 Hz
3,000 pulse (fully open)
0 pulse
Ta < 20˚C: OFF
(68˚F)
Ta ≥ 20˚C: Step4
+3step/15 sec. (Pc > 2.16 MPa (313 psi))
(68˚F)
–3step/15 sec. (Pc < 1.77 MPa (257 psi))
Step 15
Pc – Pe > 0.17 MPa (24.7 psi)
Frequency (Hz)
A
B
C
D
E
Pc – Pe > 0.78 MPa (113 psi)
Pc – Pe > 0.39 MPa (56.6 psi)
&
OR
164 Hz or more
DSH > 10˚C (18˚F)
SiUS371614E
REYQ72TA
REYQ96-168TA
60
52
75
74
90
90
120
120
180
164
Functions and Control