Daikin REYQ-TA Series Service Manual page 161

Heat recovery 60 hz
Table of Contents

Advertisement

SiUS371614E
[2-81]: Cooling comfort setting
1 (default)
This setting is used in conjunction with setting [2-8] and [2-47].
[2-82]: Heating comfort setting
1 (default)
This setting is used in conjunction with setting [2-9].
[2-97]: Auxiliary heater maximum allowable temperature
Auxiliary heater is allowed to energize when the ambient temperature is smaller than the auxiliary heater
maximum allowable temperature.
7 (default)
[2-98]: Auxiliary heater maximum allowable temperature release differential
Auxiliary heater is not allowed to energize when the outdoor ambient temperature is recovered by
differential above the auxiliary heater maximum allowable temperature.
1 (default)
Field Settings
Value
[2-81]
0
2
3
Value
[2-82]
0
2
3
Value
Auxiliary heater maximum allowable
[2-97]
0
1
2
3
4
5
6
8
9
10
11
12
13
14
Auxiliary heater always not allowed
15
Auxiliary heater always allowed
Value
Auxiliary heater maximum allowable
[2-98]
temperature release differential
0
2
Cooling comfort setting
Eco
Mild
Quick
Powerful
Heating comfort setting
Eco
Mild
Quick
Powerful
temperature
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
Field Setting from Outdoor Unit
148