Daikin REYQ-TA Series Service Manual page 157

Heat recovery 60 hz
Table of Contents

Advertisement

SiUS371614E
[2-30]: Power consumption limitation level (step 1) via the external control adaptor (DTA104A61/62)
If the system needs to be running under power consumption limitation conditions when an external
signal is sent to the unit, this setting defines the level power consumption limitation that will be applied
for step 1. The level is according to the table.
3 (default)
[2-31]: Power consumption limitation level (step 2) via the external control adaptor (DTA104A61/62)
If the system needs to be running under power consumption limitation conditions when an external
signal is sent to the unit, this setting defines the level power consumption limitation that will be applied
for step 2. The level is according to the table.
1 (default)
[2-32]: Forced, all time, power consumption limitation operation (no external control adaptor is required to
perform power consumption limitation)
If the system always needs to be running under power consumption limitation conditions, this setting
activates and defines the level power consumption limitation that will be applied continuously. The level
is according to the table.
0 (default)
Field Settings
Value
Power consumption limitation
[2-30]
1
2
4
5
6
7
8
Value
Power consumption limitation
[2-31]
2
3
Value
[2-32]
1
2
(approximately)
60%
65%
70%
75%
80%
85%
90%
95%
(approximately)
40%
50%
55%
Restriction reference
Function not active
Follows [2-30] setting
Follows [2-31] setting
Field Setting from Outdoor Unit