Outline of Control (Indoor Unit)
9.2

Set Temperature and Control Temperature

9.2.1 Without Optional Infrared Presence/Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
91
When the suction air thermistor is used for controlling (Default), the control target temperature is
determined as follows to prevent insufficient heating in heating operation.
Control target temperature: remote controller displayed temperature + 2°C (3.6°F).
The temperature difference for cooling ⇔ heating mode switching is 5°C (9°F).
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
When using the remote controller thermistor (Field setting is required)
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature