Daikin REYQ-TA Series Service Manual page 166

Heat recovery 60 hz
Table of Contents

Advertisement

Field Setting from Outdoor Unit
B. When the Normal demand operation is carried out. (Use of the external control adaptor for outdoor
unit is not required.)
1. While in setting mode 2, make setting of the set item No. 32 (Setting of alternate demand) to ON.
2. While in setting mode 2, select the set item No. 30 (Setting of Demand 1 level) and then set the setting
condition to targeted mode.
Image of operation in the case of A
Power consumption
Rated power consumption
70 % of rated power
consumption
40 % of rated power
consumption
Forced thermostat OFF
(Fan operation)
Image of operation in the case of B
Power consumption
Rated power consumption
70 % of rated power
consumption
153
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
To other external control adaptor
for outdoor unit
Demand level 1
Power consumption set by
"Demand 1 level setting".
The power consumption set with "Demand 1 level setting".
F1
F2
N
P
Demand
1
2
3 C
Host computer monitor panel or demand controller
Demand level 2
instructing
instructing
X1M
Low
noise
Outside
wiring
indicated by
dotted line.
Demand level 3
instructing
SiUS371614E
The power
consumption
during the
demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power
consumption" has
been set at
factory.)
When the
"Normal demand
setting" is set to
ON ("OFF" has
been set at
factory.), the
power
consumption can
be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at
factory.)
Field Settings