SiUS371614E 1. Safety Cautions..................vii 1.1 Warnings and Cautions Regarding Safety of Workers........ vii 1.2 Warnings and Cautions Regarding Safety of Users........ix 2. Icons Used ....................xii Part 1 General Information .............. 1 1. Model Names of Indoor/Outdoor Units............2 1.1 Indoor Unit....................
Page 5
SiUS371614E 9. Outline of Control (Indoor Unit) ..............89 9.1 Operation Flowchart ................... 89 9.2 Set Temperature and Control Temperature ..........91 9.3 Remote Controller Thermistor ..............93 9.4 Thermostat Control..................95 9.5 Drain Pump Control..................98 9.6 Control of Electronic Expansion Valve ............. 100 9.7 Freeze-up Prevention................
Page 6
SiUS371614E 3.2 Indoor Unit PCB Abnormality ..............172 3.3 Drain Level Control System Abnormality..........173 3.4 Fan Motor Lock, Overload................ 175 3.5 Indoor Fan Motor Abnormality..............178 3.6 Overload/Overcurrent/Lock of Indoor Fan Motor........182 3.7 Blower Motor Not Running ............... 183 3.8 Indoor Fan Motor Status Abnormality............
Page 7
SiUS371614E 3.48 Power Supply Voltage Imbalance ............242 3.49 Reactor Temperature Abnormality ............244 3.50 Inverter Radiation Fin Temperature Abnormality ........245 3.51 Field Setting after Replacing Outdoor Unit Main PCB Abnormality or Combination of PCB Abnormality............. 246 3.52 Refrigerant Shortage ................247 3.53 Reverse Phase, Open Phase..............
Safety Cautions SiUS371614E 1. Safety Cautions Be sure to read the following safety cautions before conducting repair work. After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer. Caution Items The caution items are classified into Warning and...
Page 9
SiUS371614E Safety Cautions Warning Do not turn the air conditioner on or off by plugging in or unplugging the power cable. Plugging or unplugging the power cable to operate the equipment may cause an electrical shock or fire. Be sure to wear a safety helmet, gloves, and a safety belt when working in a high place (more than 2 m (6.5 ft)).
Safety Cautions SiUS371614E Caution Be sure to check that the refrigerating cycle section has cooled down enough before conducting repair work. Working on the unit when the refrigerating cycle section is hot may cause burns. Conduct welding work in a well-ventilated place. Using a welder in an enclosed room may cause oxygen deficiency.
Page 11
SiUS371614E Safety Cautions Warning When wiring between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable. If the cover is not mounted properly, the terminal connection section may cause an electrical shock, excessive heat generation or fire.
Page 12
Safety Cautions SiUS371614E Caution Do not install the equipment in a place where there is a possibility of combustible gas leaks. If combustible gas leaks and remains around the unit, it may cause a fire. Check to see if parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure.
SiUS371614E Icons Used 2. Icons Used The following icons are used to attract the attention of the reader to specific information. Icon Type of Description Information Warning A warning is used when there is danger of personal injury. Warning Caution A caution is used when there is danger that the reader, through incorrect manipulation, may damage equipment, lose data, get Caution...
SiUS371614E Part 1 General Information 1. Model Names of Indoor/Outdoor Units............2 1.1 Indoor Unit....................2 1.2 DOAS Unit....................2 1.3 Outdoor Unit ....................2 1.4 Air Treatment Equipment ................4 1.5 Branch Selector Unit ..................4 2. External Appearance................... 5 2.1 Indoor Unit....................
SiUS371614E Model Names of Indoor/Outdoor Units 1. Model Names of Indoor/Outdoor Units Indoor Unit Capacity Range (ton) 1.25 Power Supply, Capacity Index Standard Ceiling Mounted Cassette FXFQ 07T — — — — — — (Round Flow with Sensing) Type Ceiling Mounted Cassette FXFQ —...
Page 16
Model Names of Indoor/Outdoor Units SiUS371614E 1.3.1 Combination of Outdoor Units (Heat Recovery 460 V) REYQ-TAYDU Model name REYQ72TAYDU REYQ96TAYDU REYQ120TAYDU REYQ144TAYDU REYQ168TAYDU Outdoor unit 1 REYQ72TAYDU REYQ96TAYDU REYQ120TAYDU REYQ144TAYDU REYQ168TAYDU Model name REYQ192TAYDU REYQ216TAYDU REYQ240TAYDU REYQ264TAYDU REYQ288TAYDU Outdoor unit 1 REYQ72TAYDU REYQ96TAYDU REYQ96TAYDU...
SiUS371614E Model Names of Indoor/Outdoor Units Air Treatment Equipment Outdoor Air Processing Unit Series Model Name Power Supply, Standard FXMQ 48MF 72MF 96MF Energy Recovery Ventilator (VAM series) Series Model Name Power Supply, Standard 300G 470G 600G 1200G : 1 phase, 208/230 V, 60 Hz U(VJU) : Standard Symbol Branch Selector Unit Single Branch Selector Unit for Heat Recovery...
External Appearance SiUS371614E 2. External Appearance Indoor Unit Ceiling mounted cassette (Round flow with sensing) type Ceiling mounted duct type FXFQ-T FXMQ-M Shown with BYCQ125B-W1 Ceiling mounted cassette (Round flow) type Ceiling suspended type FXFQ-P FXHQ-M Shown with BYCP125K-W1 4 way ceiling mounted cassette (2’×2’) type Wall mounted type FXZQ-M FXAQ-P...
SiUS371614E External Appearance DOAS Unit DVSV05/10/12 Outdoor Unit Single Outdoor Unit REYQ72TAYDU REYQ96/120/144/168TAYDU REYQ72TATJU REYQ96/120/144/168TATJU Double Outdoor Unit REYQ192TAYDU REYQ216/240/264/288/312/336TAYDU REYQ192TATJU REYQ216/240/264/288/312/336TATJU General Information...
External Appearance SiUS371614E Triple Outdoor Unit REYQ360/384/408/432/456TAYDU REYQ360/384/408/432/456TATJU Air Treatment Equipment Outdoor air processing unit Energy recovery ventilator (VAM series) FXMQ-MF VAM-G Branch Selector Unit Single branch selector unit Multi branch selector unit BS-Q54T BSQ-T General Information...
SiUS371614E Combination of Outdoor Units 3. Combination of Outdoor Units System capacity Module Number of Outdoor Unit Multi Connection units Piping Kit 21.1 28.1 12.5 35.2 — 42.2 17.5 49.2 56.3 22.5 63.3 70.3 27.5 77.4 BHFP26P100U 84.4 32.5 91.4 98.5 37.5 105.5...
Capacity Range SiUS371614E 4. Capacity Range Combination Ratio Total capacity index of the indoor units Combination ratio = Capacity index of the outdoor units Max. combination ratio Type of connected air treatment Types of connected indoor units equipments Min. Type combination When using FXMQ-MF...
SiUS371614E Capacity Range Limitation of Capacity Index for Heat Recovery Single Branch Selector unit Model BSQ36TVJ BSQ60TVJ BSQ96TVJ Maximum number of connectable indoor units unit ≤ 36 36 < unit ≤ 60 60 < unit ≤ 96 Total capacity index of connectable indoor units Multi Branch Selector unit Model BS4Q54TVJ...
SiUS371614E Refrigerant Circuit 1. Refrigerant Circuit Outdoor Unit 1.1.1 REYQ72TAYDU, REYQ72TATJU No. in Electric piping Name Major function symbol diagram Inverter compressor is operated on frequencies between 52 Hz to 210 Hz by using the Inverter compressor inverter. Compressor operation steps: Refer to page 66~ Because the system is an air heat exchange type, the fan is operated at 9-step rotation Inverter fan speed by using the inverter.
Page 27
SiUS371614E Refrigerant Circuit 1.1.2 REYQ96-168TAYDU, REYQ96-168TATJU No. in Electric piping Name Major function symbol diagram Inverter compressor Inverter compressor is operated on frequencies between 52 Hz to 210 Hz by using the inverter. Compressor operation steps: Refer to page 66~ Inverter compressor Because the system is an air heat exchange type, the fan is operated at 9-step rotation Inverter fan...
SiUS371614E Refrigerant Circuit Indoor Unit Symbol No. in piping Except Name Function diagram FXMQ-PB, FXMQ-PB FXTQ-TA FXTQ-TA Used for gas superheated degree control while Electronic expansion in cooling or subcooled degree control while in valve heating. Suction air thermistor R1T (∗1) Used for thermostat control.
Page 30
Refrigerant Circuit SiUS371614E FXMQ-PB FXTQ-TA Gas piping connection port Indoor heat exchanger Liquid piping connection port Filter Filter C: 4D034245P C: 4D068194 Refrigerant Circuit...
SiUS371614E Refrigerant Circuit Outdoor-Air Processing Unit Gas pipe connection port Heat exchanger Filter Capillary tube Distributor Solenoid valve Liquid pipe connection port Check valve Filter Filter Electronic expansion valve C: 4D018650D No. in Electric piping Name Function symbol diagram Used to control the flow rate of refrigerant, and make the Electronic expansion valve SH control (∗1) while in cooling.
Refrigerant Circuit SiUS371614E Branch Selector Unit 1.4.1 Single Branch Selector Unit BSQ36-96TVJ Electric Name Function symbol Opens while in heating operation or all indoor units are in cooling. Electronic expansion valve (EVH) (Max : 760 pulse) Electronic expansion valve (EVL) Opens while in cooling.
Page 33
SiUS371614E Refrigerant Circuit 1.4.2 Multi Branch Selector Unit BS4Q54TVJ Electronic Expansion Valve (HP/LP gas) Electronic Expansion Valve Filter Gas pipe Double pipe heat (Subcooling) Electronic Expansion Valve (Suction) Filter connection port exchanger Liquid pipe connection port Electronic Expansion Valve (HP/LP gas) Electronic Expansion Valve Filter...
Refrigerant Flow for Each Operation Mode SiUS371614E 3. Refrigerant Flow for Each Operation Mode REYQ72TAYDU, REYQ72TATJU 3.1.1 Cooling Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 45
SiUS371614E Refrigerant Flow for Each Operation Mode 3.1.2 Heating Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 46
Refrigerant Flow for Each Operation Mode SiUS371614E 3.1.3 Simultaneous Cooling and Heating Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 47
SiUS371614E Refrigerant Flow for Each Operation Mode 3.1.4 Cooling Oil Return Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 48
Refrigerant Flow for Each Operation Mode SiUS371614E 3.1.5 Defrost Heating Oil Return Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 49
SiUS371614E Refrigerant Flow for Each Operation Mode 3.1.6 Oil Return Operation at Simultaneous Cooling and Heating Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Refrigerant Flow for Each Operation Mode SiUS371614E REYQ96-168TAYDU, REYQ96-168TATJU 3.2.1 Cooling Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 51
SiUS371614E Refrigerant Flow for Each Operation Mode 3.2.2 Heating Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 52
Refrigerant Flow for Each Operation Mode SiUS371614E 3.2.3 Simultaneous Cooling and Heating Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 53
SiUS371614E Refrigerant Flow for Each Operation Mode 3.2.4 Cooling Oil Return Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 54
Refrigerant Flow for Each Operation Mode SiUS371614E 3.2.5 Defrost Heating Oil Return Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Page 55
SiUS371614E Refrigerant Flow for Each Operation Mode 3.2.6 Oil Return Operation at Simultaneous Cooling and Heating Operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas Low temperature, low pressure liquid Stop valve ( With service port φ5/16in. ( 7.9mm ) flare connection ) Check valve Check valve Liquid...
Names and Functions SiUS371614E 2. Names and Functions BRC1E73 1. Operation mode selector button 11. LCD (with backlight) 4. Up button 5. Down button 6. Right button 7. Left button 9. Operation lamp 8. On/Off button 3. Menu/OK button 10. Cancel button 2.
Page 59
SiUS371614E Names and Functions 4. Up button Used to raise the setpoint. The item above the current selection will be highlighted. (The highlighted items will be scrolled continuously when the button is continuously pressed.) Used to change the selected item. 5.
Names and Functions SiUS371614E Wireless Remote Controller ON OFF DOWN ON OFF TEMP TIME DOWN RESERVE CANCEL TIMER TEST MODE SWING TEST TEST DISPLAY (SIGNAL TRANSMISSION) FAN SPEED CONTROL BUTTON Press this button to select the fan speed, HIGH or This lights up when a signal is being transmitted.
SiUS371614E MAIN/SUB Setting 3. MAIN/SUB Setting BRC1E73 Situation The MAIN/SUB setting is necessary when 1 indoor unit is controlled by 2 remote controllers. When you use 2 remote controllers (control panel and separate remote controller), set one to MAIN and the other to SUB. Setting The remote controllers are factory setting to MAIN, so you only have to change one remote controller from MAIN to SUB.
MAIN/SUB Setting SiUS371614E Wireless Remote Controller Introduction To set the wireless remote controller, you have to set the address for: The receiver of the wireless remote controller The wireless remote controller. Setting the Address for the Receiver The address for the receiver of the wireless remote controller is factory setting to 1. To change this setting, proceed as follows: Set the wireless address switch (SS2) on the PCB according to the table below.
SiUS371614E Centralized Control Group No. Setting 4. Centralized Control Group No. Setting BRC1E73 In order to conduct the centralized remote control using the central remote controller and the unified ON/OFF controller, Group No. settings should be made by group using the operating remote controller. Make Group No.
Page 64
Centralized Control Group No. Setting SiUS371614E Note: For setting group No. of Energy recovery ventilator and wiring adaptor for other air conditioners, etc., refer to the instruction manual. NOTICE Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the installation table with the operation manual for maintenance.
SiUS371614E Centralized Control Group No. Setting Wireless Remote Controller Group No. setting by wireless remote controller for centralized control 1. When in the normal mode, press INSPECTION/TEST button for 4 seconds or more to enter field setting mode. 2. Set mode No. 00 with MODE button. 3.
Centralized Control Group No. Setting SiUS371614E Group No. Setting Example Centralized Remote Controller Indoor/Outdoor Outdoor/Outdoor Indoor/Outdoor Outdoor/Outdoor F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 Group Control by Remote Controller Main 1-00...
SiUS371614E Service Mode 5. Service Mode BRC1E73 Operating the remote controller allows service data to be acquired and various services to be set. Basic screen is displayed. Press the Cancel Press the button. Cancel Press and hold the Cancel button button for 4 seconds or more.
Page 68
Service Mode SiUS371614E Maintenance Menu Item 2 Remarks Indoor Unit Status 10.FLOAT FLOAT SWITCH ON/OFF 11.T1/T2 T1/T2 input from outside ON/OFF 12.Th1 Suction air thermistor 13.Th2 Heat exchanger liquid pipe thermistor 14.Th3 Heat exchanger gas pipe thermistor 15.Th4 Discharge air thermistor 16.Th5 —...
SiUS371614E Part 4 Functions and Control 1. Operation Flowchart (Outdoor Unit) ............58 2. Stop Control ....................59 2.1 Stop due to Error ..................59 2.2 When System is in Stop Mode ..............59 2.3 Slave Unit Stops during Master Unit Operation.......... 59 3.
Page 70
SiUS371614E 9.6 Control of Electronic Expansion Valve ............. 100 9.7 Freeze-up Prevention................101 9.8 List of Swing Flap Operations ..............103 9.9 Hot Start Control (In Heating Only) ............104 9.10 Louver Control for Preventing Ceiling Dirt..........105 9.11 Heater Control (Except FXTQ-TA Models)..........106 9.12 Heater Control (FXTQ-TA Models)............
SiUS371614E Operation Flowchart (Outdoor Unit) 1. Operation Flowchart (Outdoor Unit) For detailed description of each function in the flow below, refer to the details on related function on the following pages. Stop control (1) Stop due to error (2) When system is in stop mode (3) Slave unit stops during master unit operation Special control Standby control...
Stop Control SiUS371614E 2. Stop Control Stop due to Error In order to protect compressors, if any of the abnormal state occurs, the system will stop with thermostat OFF and the error will be determined when the retry times reaches certain number. (Refer to "Error code and Descriptions"...
SiUS371614E Standby Control 3. Standby Control Restart Standby Used to forcedly stop the compressor for a period of 2 minutes, in order to prevent the frequent ON/OFF of the compressor and equalize the pressure within the refrigerant system. In addition, the outdoor fan carry out the residual operation for a while to suppress the acceleration of the pressure equalizing and melting of the refrigerant to the evaporator.
Startup Control SiUS371614E 4. Startup Control This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor. To avoid stresses to the compressor due to oil return or else after the startup, the following control is made and the position of the four way valve is also determined.
SiUS371614E Startup Control Startup Control in Heating Frequency step up 5 sec. interval Frequency (Hz) REYQ72TA REYQ96-168TA +3 Hz/5 sec. Inverter compressor 1 0 Hz (M1C) +3 Hz/5 sec. Inverter compressor 2 0 Hz (M2C) ∗ REYQ96-168TA only PI control Initial opening Electronic expansion...
Basic Control SiUS371614E 5. Basic Control Normal Operation Electric Symbol Function of Functional Part Normal Part Name REYQ REYQ72TA Normal Cooling Normal Heating Simultaneous 96-168TA Cooling / Heating PI control, High PI control, High PI control, High pressure protection, pressure protection, pressure protection, Low pressure Low pressure...
SiUS371614E Basic Control Compressor PI Control Carries out the compressor capacity PI control to maintain Te at constant during cooling operation and Tc at constant during heating operation to ensure stable unit performance. On multi-outdoor-unit systems, this control is made according to values of the first-priority unit, which is detected with the pressure sensor.
SiUS371614E Basic Control Compressor Step Control Compressor operations vary with the following steps according to information in Compressor PI Control on page 64. Furthermore, the operating priority of compressors is subject to information in Operation Priority and Rotation of Compressors on page 64. Single unit installation REYQ72TA Step No.
Page 80
Basic Control SiUS371614E REYQ96/120TA Step Step up (Hz) Step down (Hz) Step Step up (Hz) Step down (Hz) Step Step up (Hz) Step down (Hz) 52.0 52.0 120.8 56.4 64.4 154.4 164.4 154.4 164.4 52.8 52.8 122.4 56.6 66.0 156.6 166.6 156.6 166.6...
Page 81
SiUS371614E Basic Control REYQ144/168TA Step Step up (Hz) Step down (Hz) Step Step up (Hz) Step down (Hz) Step Step up (Hz) Step down (Hz) 52.0 52.0 116.0 54.2 61.8 132.8 140.7 132.8 140.7 52.8 52.8 117.6 55.0 62.7 140.4 148.8 140.4 148.8...
Basic Control SiUS371614E Electronic Expansion Valve PI Control Main electronic expansion valve EVM control When the outdoor unit heat exchanging is performed via the condenser (Y5S or Y6S is set to OFF), this function is used to exert PI control on the electronic expansion valve (Y1E or Y3E) so that the condenser outlet subcooled degree (SC) will become constant.
SiUS371614E Basic Control Step Control of Outdoor Fans Used to control the revolutions of outdoor fans in the steps listed in table below, according to condition changes. REYQ72TA REYQ96TA Standard (default) Standard (default) Step No. Heating, Heating, Cooling Step No. Cooling Simultaneous Simultaneous...
SiUS371614E Basic Control Heat Exchanger Control While in heating or cool/heat simultaneous operation, ensure target condensing and evaporating temperature by changing over the air heat exchange of outdoor unit to the evaporator or the condenser in response to loads. Single system Outdoor unit Outdoor unit Lower side...
Protection Control SiUS371614E 6. Protection Control High Pressure Protection Control This high pressure protection control is used to prevent the activation of protection devices due to abnormal increase of high pressure and to protect compressors against the transient increase of high pressure.
Page 87
SiUS371614E Protection Control Heating Normal Operation < 3.17 MPa > 3.31 MPa (460 psi) (480 psi) Pc: High pressure sensor detection value for master > 3.39 MPa unit All units (492 psi) Compressor step: 1 9-step down After 10 > 3.31 MPa seconds (480 psi)
Protection Control SiUS371614E Low Pressure Protection Control This low pressure protection control is used to protect compressors against the transient decrease of low pressure. Cooling Normal Operation < 0.25 MPa > 0.39 MPa (36.3 psi) (56.6 psi) Pe: Low pressure sensor detection value for master unit All compressors step.: 1...
SiUS371614E Protection Control Discharge Pipe Protection Control This discharge pipe protection control is used to protect the compressor internal temperature against an error or transient increase of discharge pipe temperature. HTdi > 115˚C Upper limit compressor step: (239˚F) max (Max. Step) HTdi: Value of inverter compressor Normal Operation discharge pipe temperature...
Protection Control SiUS371614E Compressor Body Protection Control This compressor body protection control is used to protect the compressor internal temperature against an error or transient increase of compressor body temperature. Contents The following control is performed for each compressor of single unit as well as multi units. Inverter compressor (only for type JT15JBVDKYR) Normal operation Compressor body...
SiUS371614E Protection Control Inverter Protection Control Inverter current protection control and radiation fin temperature control are performed to prevent tripping due to an error, or transient inverter overcurrent, and fin temperature increase. In the case of multi-outdoor-unit system, each inverter compressor performs these controls in the following sequence.
Page 92
Protection Control SiUS371614E Radiation fin temperature control Perform the following control of integrated as well as multi units for each inverter compressor. Normal operation Reduce compressor capacity When occurring 4 times within 60 Fin temperature standby minutes, the error code L4 is output. REYQ72TAYDU REYQ96-120TAYDU REYQ144-168TAYDU...
SiUS371614E Special Control 7. Special Control Pump Down Residual Operation Pc : High pressure sensor detection value Pe : Low pressure sensor detection value Ta : Outdoor air temperature Te : Low pressure equivalent saturation temperature HTdi : Value of inverter compressor discharge pipe temperature (Tdi) compensated with outdoor air temperature If the liquid refrigerant stays in the evaporator at the startup of a compressor, this liquid refrigerant enters the compressor, thus resulting in diluted oil in the compressor and then degraded lubrication performance.
Special Control SiUS371614E Oil Return Operation In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil that has flowed out from the compressor to the system side. Tc : High pressure equivalent saturation temperature Te : Low pressure equivalent saturation temperature TsA: Suction pipe temperature detected by thermistor R3T 7.2.1 Oil Return Operation in Cooling Operation...
Page 95
SiUS371614E Special Control 7.2.2 Oil Return Operation in Heating Operation Starting conditions Electric Symbol Part Name Oil return operation REYQ72TA REYQ96-168TA Inverter compressor 1 +1 to +6 steps from frequency to frequency when oil return is IN at a constant level Inverter compressor 2 —...
Special Control SiUS371614E Defrost Operation To defrost the outdoor heat exchanger while in Evaporator, the defrost operation is conducted to recover the heating capacity. Tb: Heat exchanger deicer temperature Electric Symbol Part Name Defrost operation REYQ72TA REYQ96-168TA REYQ72TA: 282 Hz Inverter compressor 1 REYQ96-168TA: 252 Hz + 252 Hz Inverter compressor 2...
SiUS371614E Special Control Cooling/Heating Mode Switching [While in cooling / heating mixed mode, single-room cooling → heating] First, the electronic expansion valve of the indoor unit in cooling operation will close, and the Y2E and Y3E electronic expansion valves of the branch selector unit will all close once. Next, the Y2E electronic expansion valve will open little by little to perform pressure equalization.
Page 98
Special Control SiUS371614E [While in cooling/heating mixed mode, single-room heating → cooling] First, the electronic expansion valve of the indoor unit in heating operation will close, and the Y2E and Y3E electronic expansion valves of the branch selector unit will all close once. Next, the Y3E electronic expansion valve will open little by little to perform pressure equalization.
Page 99
SiUS371614E Special Control [While in all-room cooling operation → All-room cooling/heating simultaneous operation] Dual pressure gas pipe (1) All the indoor units in cooling operation · Using the dual pressure gas pipe as a suction Suction gas pipe gas pipe. Liquid pipe (2) Pump-down residual operation...
Page 100
Special Control SiUS371614E [While in all-room heating operation or cooling/heating simultaneous operation → All-room cooling] Dual pressure gas pipe (1) In heating operation or cooling and heating simultaneous operation Suction gas pipe · Using the dual pressure gas pipe as a suction gas pipe.
SiUS371614E Other Control 8. Other Control Backup Operation If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor unit from operating, and then conduct emergency operation only with operational compressors or outdoor units. "Emergency operation with remote controller reset" and "Emergency operation with outdoor unit PCB setting"...
Outline of Control (Indoor Unit) SiUS371614E 9. Outline of Control (Indoor Unit) Operation Flowchart Cooling Operation Start (Option) Turn ON Aux. electric : OFF ∗16 power supply heater Humidifier : OFF Initialize electronic expansion valve Swing flap Detect louver lock prevention condition? The previous settings of airflow LED in remote...
Page 103
SiUS371614E Outline of Control (Indoor Unit) Program dry operation Heating Operation (option) Program ∗7 dry display Drain : OFF pump kit ∗8 Thermostat status : Operating in L mode after it stops for 6 min. Operating in L mode Swing flap? Electronic 20E : expansion valve...
Outline of Control (Indoor Unit) SiUS371614E Set Temperature and Control Temperature 9.2.1 Without Optional Infrared Presence/Floor Sensor The relationship between remote controller set temperature and control target temperature is described below. • When the suction air thermistor is used for controlling (Default), the control target temperature is determined as follows to prevent insufficient heating in heating operation.
Page 105
SiUS371614E Outline of Control (Indoor Unit) 9.2.2 With Optional Infrared Presence/Floor Sensor The relationship between remote controller set temperature and control target temperature is described below. The temperature difference for cooling ⇔ heating mode switching is 5°C (9°F). • • When using the floor temperature as the control target, the remote controller set temperature is equal to the actual control target temperature in heating operation.
Outline of Control (Indoor Unit) SiUS371614E Remote Controller Thermistor Temperature is controlled by both the remote controller thermistor and suction air thermistor for the indoor unit. (This is however limited to when the field setting for the remote controller thermistor is set to Use.) Note: When outdoor air is introduced to the air-conditioner with mixed into indoor air, the room...
Page 107
SiUS371614E Outline of Control (Indoor Unit) Heating When heating, the hot air rises to the top of the room, resulting in the temperature being lower near the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit may therefore be turned off by the thermostat before the lower part of the room reaches the set temperature.
Outline of Control (Indoor Unit) SiUS371614E Thermostat Control 9.4.1 Without Optional Infrared Presence/Floor Sensor Whether the thermostat is turned on or off is determined by the difference between the remote controller set temperature and the actual detected room temperature (∗1). Normal operation ·...
Page 109
SiUS371614E Outline of Control (Indoor Unit) 9.4.2 With Optional Infrared Presence/Floor Sensor Whether the thermostat is turned on or off is determined by the difference between the remote controller set temperature and the detected temperature around people. Normal operation · Cooling operation ∆T ≤...
Page 110
Outline of Control (Indoor Unit) SiUS371614E 9.4.3 Thermostat Control with Operation Mode Set to AUTO When the operation mode is set to AUTO on the remote controller, the system will conduct the temperature control shown below. Furthermore, setting changes of the differential value (D) can be made referring to page 114 and later (Field Setting from Remote Controller).
SiUS371614E Outline of Control (Indoor Unit) Drain Pump Control 9.5.1 Normal Operation Float switch Thermostat (running) Error display Drain pump 5 min. • The float switch is ON in normal operation. • When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously. •...
Page 112
Outline of Control (Indoor Unit) SiUS371614E 9.5.3 If the Float Switch is OFF with the Thermostat OFF in Cooling Operation Float switch Thermostat (running) Error display Drain pump 5 min. 5 sec. • When the float switch turns OFF, the drain pump turns ON simultaneously. •...
SiUS371614E Outline of Control (Indoor Unit) Control of Electronic Expansion Valve Electronic expansion valves in indoor units have the functions of conducting superheated degree control in cooling operation and subcooling degree control in heating operation. However, if the indoor units receive any control command such as a protection control command or a special control command from the outdoor unit, the units will give a priority to the control command.
Outline of Control (Indoor Unit) SiUS371614E Freeze-up Prevention Freeze-up Prevention by Off Cycle (Indoor Unit Individual Control) When the temperature detected by the liquid pipe temperature thermistor of the indoor heat exchanger drops too low, the unit enters freeze-up prevention control in accordance with the following conditions, and is also set in accordance with the conditions given below.
Page 115
SiUS371614E Outline of Control (Indoor Unit) Note: When the indoor unit is FXFQ, FXZQ or FXUQ, if the air outlet is set as dual-directional or tri- directional, the starting conditions will be changed as follows. Liquid pipe temperature ≤ 1°C (33.8°F) (for total of 15 minutes) Liquid pipe temperature ≤...
Outline of Control (Indoor Unit) SiUS371614E List of Swing Flap Operations Swing flaps operate as shown in table below. Flap FXFQ FXEQ FXHQ FXAQ Swing Horizontal Horizontal Horizontal Horizontal Hot start from defrost operation Airflow direction set Horizontal Horizontal Horizontal Horizontal Swing Horizontal...
SiUS371614E Outline of Control (Indoor Unit) Hot Start Control (In Heating Only) At startup with thermostat ON or after the completion of defrosting in heating operation, the indoor fan is controlled to prevent cold air from blasting out and ensure startup capacity. TH2: Temperature detected with the gas thermistor Tc : High pressure equivalent saturated temperature Starting condition...
Outline of Control (Indoor Unit) SiUS371614E 9.10 Louver Control for Preventing Ceiling Dirt We have added a control feature that allows you to select the range of in which air direction can be adjusted in order to prevent the ceiling surrounding the air discharge outlet of ceiling mounted cassette type units from being soiled.
SiUS371614E Outline of Control (Indoor Unit) 9.11 Heater Control (Except FXTQ-TA Models) Note: Optional PCB KRP1B ... is required. The heater control is conducted in the following manner. Normal control While in heating, the heater control (ON/ Set temperature OFF) is conducted as shown on the right. 2˚C 2˚C (3.6˚F)
Outline of Control (Indoor Unit) SiUS371614E 9.12 Heater Control (FXTQ-TA Models) Note: Optional heater kit HKS... is required. For FXTQ models, heater ON/OFF output from wiring adaptor interlocks with the operation of heater kit HKS….(When the heater 1 turns ON/OFF, heater output of wiring adaptor turns ON/OFF.) Fan residual operation also interlocks with the fan residual operation of heater kit HKS….
Page 121
SiUS371614E Outline of Control (Indoor Unit) Condition A • No fan motor system error • High pressure condition: ON (∗1) • Liquid pipe temperature condition: ON (∗2) • Heater ON permission (Defrost/oil Return): 0 (∗4) & & • Not during defrost/oil return •...
Page 122
Outline of Control (Indoor Unit) SiUS371614E 9.12.2 Heat Pump Lockout Control For heating operation, users can select to use electric heater. For this, signals are sent using ABC terminal of outdoor unit PCB. When the hot-water heating signal is received from the outdoor unit PCB, heating operation is performed only with the electric heater as manual backup operation.
SiUS371614E Outline of Control (Indoor Unit) 9.13 3 Step Thermostat Processing (FXTQ-TA Models) Outline The thermostat ON/OFF for the indoor unit is controlled in accordance with [Thermostat Step 1]. The heater ON/OFF operation during heating is controlled as follows. Thermostat step 2, 3: Auxiliary electric heater control Thermostat step 1, 2: Heat pump lockout control For more details of the heater, refer to Heater Control (FXTQ-TA Models) on page 107.
Outline of Control (Indoor Unit) SiUS371614E 9.14 Fan Control (Heater Residual) (FXTQ-TA Models) Outline If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for further period of time in order to cool the heater. Detail Residual ON •...
Page 125
SiUS371614E Outline of Control (Indoor Unit) 9.15.3 Economizer When indoor and outdoor air temperatures are reversed, the compressor is stopped to let in the outdoor air to save energy. This operation is called economizer operation, and the equipment to detect indoor and outdoor air temperatures and open and close the damper to perform this operation is called an economizer.
SiUS371614E Part 5 Field Settings 1. Field Setting from Remote Controller............114 1.1 Wired Remote Controller................114 1.2 Wireless Remote Controller ..............116 1.3 Simplified Remote Controller..............117 1.4 Setting Contents and Code No. for Indoor Units ........118 2. Field Setting from Outdoor Unit............... 136 2.1 Accessing the BS Buttons on the Logic Board.........
SiUS371614E Field Setting from Remote Controller 1. Field Setting from Remote Controller Individual function of indoor unit can be changed from the remote controller. At the time of installation or after service inspection / repair, make the field setting in accordance with the following description. Wrong setting may cause error.
Page 128
Field Setting from Remote Controller SiUS371614E Press Menu/OK button. Setting confirmation screen is displayed. <Setting confirmation screen> Select Yes and press Menu/OK button. Setting details are determined and field settings screen returns. In the case of multiple setting changes, repeat “ ”...
SiUS371614E Field Setting from Remote Controller Wireless Remote Controller UP button Mode No. Field setting mode DOWN button RESERVE button First code No. MODE button Second code No. INSPECTION/TEST button To set the field settings, you have to change: Mode No. First code No.
Field Setting from Remote Controller SiUS371614E Simplified Remote Controller Mode No. First code Unit No. Second code No. (2)(8) (7) (4) (5) (6) 1. Remove the upper part of remote controller. 2. When in the normal mode, press the BS6 button (2) (field setting) to enter the field setting mode. 3.
SiUS371614E Field Setting from Remote Controller Setting Contents and Code No. for Indoor Units : Factory setting Mode First Second Code No. Code Setting Contents (∗2) Approx. Approx. Ultra long life 10,000 5,000 Filter sign setting filter hrs. hrs. (Setting for display time to clean air filter) Approx.
Page 132
Field Setting from Remote Controller SiUS371614E Mode First Second Code No. Code Setting Contents (∗2) Setting of airflow rate Standard High ceiling 1 High ceiling 2 — Airflow direction setting F (4 directions) T (3 directions) — (Set when a blocking pad kit has been installed.) (2 directions) All direction Swing pattern settings...
Page 133
SiUS371614E Field Setting from Remote Controller 1.4.1 Applicable Range of Field setting Ceiling mounted 4-way blow One way Slim Ceiling Ceiling Wall Floor Concealed cassette type ceiling blow ceiling mounted suspended mounted standing floor handling suspended cassette mounted duct type type type type...
Page 134
Field Setting from Remote Controller SiUS371614E 1.4.2 Detailed Explanation of Setting Modes Filter Sign Setting If switching the filter sign ON time, set as given in the table below. First Code Second Standard Long Life Ultra Long Life Mode No. Contents Code No.
Page 135
SiUS371614E Field Setting from Remote Controller (˚F) (˚C) 96.8 93.2 In cooling 89.6 Suction air Remote controller Suction air thermistor thermistor thermistor Suction air Suction air Remote controller 82.4 thermistor thermistor thermistor 78.8 75.2 71.6 (˚C) 62.6 66.2 69.8 73.4 80.6 84.2 87.8 91.4 98.6 (˚F)
Page 136
Field Setting from Remote Controller SiUS371614E Filter Cleaning Sign Whether or not to display "Filter Cleaning" after operation of certain duration can be selected. Mode No. First Code No. Second Code No. Contents Displayed 10 (20) Not displayed ∗ Filter cleaning sign is not displayed when an Auto-clean Panel is connected. Time for Absence Area Detection (For units with an infrared presence/floor sensor only) By selecting the energy-saving operation mode in the absence, the target temperature is shifted to the energy-...
Page 137
SiUS371614E Field Setting from Remote Controller Auxiliary Electric Heater ON/OFF Temperature Thermostat Set temperature Thermostat Toff + S (∗1) Ton + S (∗1) Note: ∗1. S value varies automatically based on the room temperature trend. FXFQ-T, FXMQ-PB Second Code No. Mode No.
Page 138
Field Setting from Remote Controller SiUS371614E Setting the Airflow Rate when Heating The fan revolution is changed to maintain the sufficient distance for warm air to reach during the heating operation. The setting should be changed depending on the installation condition of the unit. Second Code No.
Page 139
SiUS371614E Field Setting from Remote Controller Setting the Rate of Human Detection (For units with the infrared presence/floor sensor only) Set the sensitivity of the infrared presence sensor. • The infrared presence sensor can be disabled by selecting the Second code No. 04. (Note) When the infrared presence sensor is disabled, the remote controller menu does not display some functions such as the automatic draft reduction, energy-saving operation in absence and halt in absence.
Page 140
Field Setting from Remote Controller SiUS371614E Compensating the Floor Temperature (For units with the infrared presence/floor sensor only) Offset the detected value of the infrared floor sensor with a certain temperature. This setting should be used to have the actual floor temperature detected when, for example, the unit is installed close to a wall. Mode No.
Page 141
SiUS371614E Field Setting from Remote Controller Thermostat Switching Differential value during thermostat ON/OFF control can be changed. Mode No. First Code No. Second Code No. Contents 1°C (1.8°F) 12(22) 0.5°C (0.9°F) Airflow Setting when Heating Thermostat is OFF This setting is used to set airflow when heating thermostat is OFF. ∗...
Page 142
Field Setting from Remote Controller SiUS371614E Setting of Airflow Rate Make the following setting according to the ceiling height. The second code No. is set to 01 at the factory. FXHQ, FXAQ Mode No. First Code No. Second Code No. Contents Standard 13 (23)
Page 143
SiUS371614E Field Setting from Remote Controller Operation of Downward Flow Flap (for FXEQ model) When only the front-flow is used, sets yes/no of the swing flap operation of down-flow Model No. First Code No. Second Code No. Contents Equipped 13 (23) Not equipped Setting of Airflow Direction Adjustment Range Make the following airflow direction setting according to the respective purpose.
Page 144
Field Setting from Remote Controller SiUS371614E Optional Kit Setting (UV lamp + Humidifier + Economizer) (for FXTQ-TA model) Contents Economizer setting for Mode No. First Code No. Second Code No. UV lamp + humidifier fan Mech standby duration speed (minutes) Refer to controller High Refer to controller...
Page 145
Contents Not equipped 15 (25) Individual operation of ventilation Display of Contact Center (For BRC1E73 only) You can turn OFF the display of "DAIKIN Contact Center" as "Contact for Service Display." Mode No. First Code No. Second Code No. Contents...
Page 146
Field Setting from Remote Controller SiUS371614E Setting "Restricted / Permitted" of Airflow Block (For units with the infrared presence/floor sensor only) Due to possibility of dew condensation, the airflow block function cannot be enabled when closure material kit, fresh air intake kit, natural / separately installed evaporation humidifier, or branch air duct is equipped. This setting will prevent the airflow block is advertently set to ON.
Page 147
SiUS371614E Field Setting from Remote Controller 1.4.3 Outdoor-Air Processing Unit - Field Setting (Remote Controller) : Factory setting First Second Code No. Mode Setting Contents Code Filter contamination 2500 hr 1250 hr — — — — — — — — —...
Page 148
Field Setting from Remote Controller SiUS371614E How to Select Operation Mode Whether operation by remote controller will be possible or not for turning ON/OFF, controlling temperature or setting operation mode is selected and decided by the operation mode given on the right edge of the table below. Example ON by remote OFF by remote...
SiUS371614E Field Setting from Outdoor Unit 2. Field Setting from Outdoor Unit To continue the configuration of the VRV IV heat recovery system, it is required to give some input to the logic board of the unit. This chapter will describe how manual input is possible by operating the BS buttons/DIP switches on the logic board and reading the feedback from the 7 segment displays.
Field Setting from Outdoor Unit SiUS371614E Operating the BS Buttons and DIP Switches on the Logic Board Operating the BS buttons By operating the BS buttons it is possible to: • Perform special actions (testrun, etc). • Perform field settings (demand operation, low noise, etc). Below procedure explains how to operate the BS buttons to reach the required mode in the menu, select the correct setting and modify the value of the setting.
Page 151
SiUS371614E Field Setting from Outdoor Unit Accessing modes BS1 is used to change the mode you want to access. • Access mode 1 Press BS1 once. Segment indication changes to: • Access mode 2 Press BS1 for at least 5 seconds. Segment indication changes to: INFORMATION If you get confused in the middle of the process, press BS1.
Field Setting from Outdoor Unit SiUS371614E Example: Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor unit's fan). Mode: 2 Setting: 18 • Make sure the segment indication is as during normal operation (default situation when shipped from factory). •...
SiUS371614E Field Setting from Outdoor Unit Monitoring Function and Field Settings The operation of the outdoor unit can further be defined by changing some field settings. Next to making field settings it is also possible to confirm the current operation parameters of the unit. The setting can also be performed via the PC configuration software.
Page 154
Field Setting from Outdoor Unit SiUS371614E [1-5]: shows the current Te target parameter position. [1-6]: shows the current Tc target parameter position. [1-10]: shows the total number of connected indoor units. It can be convenient to check if the total number of indoor units which are installed match the total number of indoor units which are recognized by the system.
Page 155
SiUS371614E Field Setting from Outdoor Unit [2-9]: Tc target temperature during heating operation Value Tc target [2-9] 0 (default) Auto 41°C (105.8°F) 42°C (107.6°F) 43°C (109.4°F) 46°C (114.8°F) [2-12]: Enable the night-time low noise function and/or power consumption limitation via external control adaptor (DTA104A61/62) If the system needs to be running under night-time low noise operation or under power consumption limitation conditions when an external signal is sent to the unit, this setting should be changed.
Page 156
Field Setting from Outdoor Unit SiUS371614E [2-21]: Refrigerant recovery/vacuuming mode In order to achieve a free pathway to reclaim refrigerant out of the system or to remove residual substances or to vacuum the system it is necessary to apply a setting which will open required valves in the refrigerant circuit so the reclaim of refrigerant or vacuuming process can be done properly.
Page 157
SiUS371614E Field Setting from Outdoor Unit [2-30]: Power consumption limitation level (step 1) via the external control adaptor (DTA104A61/62) If the system needs to be running under power consumption limitation conditions when an external signal is sent to the unit, this setting defines the level power consumption limitation that will be applied for step 1.
Page 158
Field Setting from Outdoor Unit SiUS371614E [2-34]: Indoor fan tap setting Indoor fan speed limitation related to connection capacity and outdoor air temperature for energy saving. Value Indoor fan tap setting [2-34] Fan speed is limited to L tap when indoor units 0 (default) capacity ≥...
Page 159
SiUS371614E Field Setting from Outdoor Unit [2-37]: Heat pump lockout 2 Heat pump is locked out when this setting and an external input to ABC terminal are made. Automatic lockout When this setting is made, the auto-backup function will automatically be activated. This will allow the auxiliary or secondary heat source to be automatically energized in the event of a system failure related to outdoor units.
Page 160
Field Setting from Outdoor Unit SiUS371614E [2-49]: Height difference setting Default value: 0. In case the outdoor unit is installed in the highest position (indoor units are installed on a lower position than outdoor units) and the height difference between the lowest indoor unit and the outdoor unit exceeds 50 m (164 ft), the setting [2-49] has to be changed to 1.
Page 161
SiUS371614E Field Setting from Outdoor Unit [2-81]: Cooling comfort setting Value Cooling comfort setting [2-81] 1 (default) Mild Quick Powerful This setting is used in conjunction with setting [2-8] and [2-47]. [2-82]: Heating comfort setting Value Heating comfort setting [2-82] 1 (default) Mild Quick...
Field Setting from Outdoor Unit SiUS371614E Cool / Heat Mode Changeover Set Cool/Heat Separately for Each Branch Selector Unit by Cool/Heat Selector. Set remote controller changeover switch (SS1, SS2) as following: • When using COOL/HEAT selector, turn this switch to the BS side. NOTE: This setting must be completed before turning power supply ON.
SiUS371614E Field Setting from Outdoor Unit Setting of Night-time Low Noise Operation and Demand Operation Setting of Night-time Low Noise Operation By connecting the external contact input to the low noise input of the outdoor unit external control adaptor (optional), you can lower operating noise. Setting Content Level 1...
Page 164
Field Setting from Outdoor Unit SiUS371614E Image of operation in the case of A Operation If capacity priority is set in sound Capacity priority setting, the fan speed will be increased according to the load of air conditioning when load is heavier. Rated operation Operation sound during sound...
Page 165
SiUS371614E Field Setting from Outdoor Unit Setting of Demand Operation By connecting the external contact input to the demand input of the outdoor unit external control adaptor for outdoor unit (optional), the power consumption of unit operation can be saved suppressing the compressor operating condition.
Page 166
Field Setting from Outdoor Unit SiUS371614E B. When the Normal demand operation is carried out. (Use of the external control adaptor for outdoor unit is not required.) 1. While in setting mode 2, make setting of the set item No. 32 (Setting of alternate demand) to ON. 2.
Page 167
SiUS371614E Field Setting from Outdoor Unit Image of operation in the case of A and B The power Power consumption consumption can be set with the "Demand 1 level setting". ("70 % of rated power Rated power consumption consumption" has been set at factory.) 70 % of rated power...
Test Operation SiUS371614E 3. Test Operation Checks before Test Operation Before carrying out a test operation, proceed as follows: Step Action Make sure the voltage at the primary side of the safety breaker is: (230 V or 460 V) ± 10% for 3-phase units Fully open the liquid and the gas stop valve.
Symptom-based Troubleshooting SiUS371614E 1. Symptom-based Troubleshooting Indoor Unit Overall Symptom Supposed Cause Countermeasure The system does not start operation at all. Blowout of fuse(s) Turn Off the power supply and then replace the fuse(s). Cutout of breaker(s) • If the knob of any breaker is in its OFF position, turn ON the power supply.
Page 173
SiUS371614E Symptom-based Troubleshooting Symptom Supposed Cause Countermeasure COOL/HEAT The remote controller displays This remote controller has no option Use a remote controller with option to select cooling operation. to select cooling operation. selection is UNDER CENTRALIZED disabled. CONTROL. The remote controller displays COOL/HEAT selection is made Use the COOL/HEAT selection using the COOL/HEAT selection...
Page 174
Symptom-based Troubleshooting SiUS371614E Symptom Supposed Cause Countermeasure 11 The system <Indoor unit> These are operating sounds of the Normal operation. produces Immediately after turning ON electronic expansion valve of the This sound becomes low after a sounds. the power supply, indoor unit indoor unit.
SiUS371614E Symptom-based Troubleshooting With Optional Infrared Presence/Floor Sensor Condition Measure 1 "Louver operation different from setting" or "No downward Refer to the following table. airflow in heating operation" 2 Individual airflow direction setting different from the actual · Check the "Louver operation different from setting" error airflow direction diagnosis.
Service Check Function SiUS371614E 2. Service Check Function Wired Remote Controller 2.1.1 BRC1E73 <Main Menu> Main Menu • Airflow Direction Airflow Direction • Individual Airflow Direction Individual Airflow Direction • Ventilation Ventilation • Schedule Schedule • Off Timer Off Timer •...
Page 177
SiUS371614E Service Check Function The following will be displayed on the screen when an error (or a warning) occurs during operation. Check the error code and take the corrective action specified for the particular model. Screen Operation lamp (1) Check if it is an error or warning. Operation Status Display The operation lamp (green) starts to...
Service Check Function SiUS371614E Wireless Remote Controller If unit stops due to an error, the operation indicating LED on the signal receiving part of indoor unit blinks. The error code can be determined by following the procedure described below. (The error code is displayed when an operation error has occurred.
Page 179
SiUS371614E Service Check Function 2. Change the UNIT No. with Normal mode UP or DOWN button. 1. Press INSPECTION/TEST button to enter the inspection mode. If no button is pressed for 1 minute, equipment returns to normal mode. 3. Press MODE button.
Service Check Function SiUS371614E Error Codes and Descriptions k: ON h: OFF l: Blink Error code Operation Error contents Reference lamp page Indoor Unit External protection device abnormality Indoor unit PCB abnormality Drain level control system abnormality Fan motor lock, overload Indoor fan motor abnormality Overload/overcurrent/lock of indoor fan motor Blower motor not running...
Page 181
SiUS371614E Service Check Function k: ON h: OFF l: Blink Error code Operation Error contents Reference lamp page Outdoor Unit Low pressure sensor abnormality Inverter PCB abnormality Reactor temperature rise abnormality Inverter radiation fin temperature rise abnormality Inverter compressor instantaneous overcurrent Inverter compressor overcurrent Inverter compressor startup abnormality Transmission error between inverter PCB and outdoor unit main PCB...
Service Check Function SiUS371614E Error Codes - Sub Codes If an error code like the one shown below is displayed when the navigation remote controller (BRC1E series) is in use, make a detailed diagnosis or a diagnosis of the relevant unit. 2.4.1 Indoor Unit Troubleshooting Error code...
SiUS371614E Troubleshooting by Error Code 3. Troubleshooting by Error Code External Protection Device Abnormality 3.1.1 External Protection Device Abnormality (All Indoor Unit Models) Error Code Applicable All indoor unit models Models Method of Error Detect open or short circuit between external input terminals in indoor unit. Detection Error Decision When an open circuit occurs between external input terminals with the remote controller set to...
Page 184
Troubleshooting by Error Code SiUS371614E 3.1.2 External Protection Device Abnormality (FXTQ-TA Only) A0-01 Error Code Applicable FXTQ-TA Models Method of Error Detect open or short circuit between external input terminals in indoor unit. Detection Error Decision When an open circuit occurs between external input terminals. Conditions Supposed Actuation of external protection device...
SiUS371614E Troubleshooting by Error Code Indoor Unit PCB Abnormality Error Code Applicable All indoor unit models Models Method of Error Check data from EEPROM. Detection Error Decision When data could not be correctly received from the EEPROM Conditions EEPROM : Type of nonvolatile memory. Maintains memory contents even when the power supply is turned OFF.
Troubleshooting by Error Code SiUS371614E Drain Level Control System Abnormality Error Code Applicable FXFQ, FXZQ, FXUQ, FXEQ, FXDQ, FXMQ-PB, FXMQ-M (Option), FXAQ (Option) Models Method of Error By float switch OFF detection Detection Error Decision When rise of water level is not a condition and the float switch goes OFF. Conditions Supposed 208~230 V power supply is not provided...
Page 187
SiUS371614E Troubleshooting by Error Code The drain pump works when Check the drain piping for the power supply is reset for clogging or upward slope, etc. the indoor unit. voltage of drain pump terminals (∗2) is 208- Replace the indoor unit main 230 V (within 5 minutes of PCB (A1P).
Troubleshooting by Error Code SiUS371614E Fan Motor Lock, Overload Error Code Applicable FXFQ, FXUQ, FXEQ, FXMQ07-12PB, FXAQ Models Method of Error Abnormal fan revolutions are detected by a signal output from the fan motor. Detection Error Decision When the fan revolutions do not increase Conditions Supposed Broken wires in, short circuit of, or disconnection of connectors from the fan motor harness...
Page 189
SiUS371614E Troubleshooting by Error Code Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Turn OFF the power supply, and then wait for a period of 10 minutes. there any Remove the foreign matter.
Page 190
Troubleshooting by Error Code SiUS371614E ∗1: Check the following connectors. Note: Model Connector FXFQ-T X20A, Relay connector FXFQ09-30P X20A, Relay connector FXFQ36/48P X20A FXUQ-A X20A, Relay connector FXEQ-P X20A FXMQ07-12PB FXAQ-P X20A ∗2. Resistance measuring points and judgment criteria. 1 — —...
SiUS371614E Troubleshooting by Error Code Indoor Fan Motor Abnormality 3.5.1 Indoor Fan Motor Abnormality (FXDQ, FXHQ Models) Error Code Applicable FXDQ, FXHQ Models Method of Error This error is detected if there is no revolutions detection signal output from the fan motor. Detection Error Decision When no revolutions can be detected even at the maximum output voltage to the fan...
Page 192
Troubleshooting by Error Code SiUS371614E 3.5.2 Indoor Fan Motor Abnormality (FXMQ15-54PB Models) Error Code Applicable FXMQ15-54PB Models Method of Error Error from the current flow on the fan PCB Detection Error from the rotation speed of the fan motor in operation Error from the position signal of the fan motor Error from the current flow on the fan PCB when the fan motor starting operation Error Decision...
Page 193
SiUS371614E Troubleshooting by Error Code Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Turn OFF the power and wait for 10 minutes. There is a Remove the foreign matter. foreign matter around the fan.
Page 194
Troubleshooting by Error Code SiUS371614E resistance among U, V, and W Replace the indoor fan motor. are unbalanced or short circuited. Remove the signal connector from the fan motor and check the resistance (∗2). Between Vcc and GND terminals, and Replace the indoor fan motor.
SiUS371614E Troubleshooting by Error Code Overload/Overcurrent/Lock of Indoor Fan Motor Error Code Applicable FXMQ-M Models Method of Error This error is detected by detecting that the individual power supply for the fan turns OFF. Detection Error Decision When it is not detected that the individual power supply for the indoor fan turns ON while in Conditions operation.
Troubleshooting by Error Code SiUS371614E Blower Motor Not Running Error Code Applicable FXTQ-TA Models Outline Error is issued if the indoor unit determines that the indoor fan motor cannot rotate, regardless of the rotation command from indoor unit. Error Decision Determining successive abnormalities Conditions Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
SiUS371614E Troubleshooting by Error Code Indoor Fan Motor Status Abnormality A6-20 Error Code Applicable FXTQ-TA Models Outline The indoor unit periodically receives control status information from the fan motor. Error is issued when the information shows abnormality. Error Decision If the information shows Power Limit or Temp Limit status, it will be deemed a MOTOR LIMIT Conditions abnormal operation.
Troubleshooting by Error Code SiUS371614E Low Indoor Airflow A6-21 Error Code Applicable FXTQ-TA Models Outline Error is issued if the indoor unit determines that the indoor fan motor rotation is insufficient, regardless of the rotation command from indoor unit. Error Decision Determining successive abnormalities Conditions Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
SiUS371614E Troubleshooting by Error Code 3.10 Swing Flap Motor Abnormality Error Code Applicable FXFQ, FXZQ, FXUQ, FXEQ, FXHQ, FXAQ Models Method of Error Utilizes ON/OFF of the limit switch when the motor turns. Detection Error Decision When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing flap Conditions motor is energized for a specified amount of time (about 30 seconds).
Page 200
Troubleshooting by Error Code SiUS371614E The relay cable has no Replace the power supply continuity. relay cable. When the airflow direction flap-cam mechanism is disconnected Replace the defective from the swing motor, swing motor. (∗2) operation is normal when turned ON again.
SiUS371614E Troubleshooting by Error Code 3.11 Power Supply Voltage Abnormality Error Code Applicable FXMQ-PB Models Method of Error Error is detected by checking the input voltage of fan motor. Detection Error Decision When the input voltage of fan motor is 150 V or less, or 386 V or more. Conditions Supposed Defective power supply voltage...
Troubleshooting by Error Code SiUS371614E 3.12 Blower Motor Stops for Over/Under Voltage Error Code Applicable FXTQ-TA Models Outline The indoor unit periodically receives control status information from the fan motor. Error is issued when the information shows abnormality. Error Decision If the information shows Over/Under Voltage status, it will be deemed a MOTOR VOLTS abnormal Conditions operation.
SiUS371614E Troubleshooting by Error Code 3.13 Electronic Expansion Valve Coil Abnormality, Dust Clogging Error Code Applicable All indoor unit models Models Method of Error Check coil condition of electronic expansion valve by using microcomputer. Detection Check dust clogging condition of electronic expansion valve main body by using microcomputer. Error Decision Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Troubleshooting by Error Code SiUS371614E 3.14 Drain Level above Limit Error Code Applicable FXFQ, FXZQ, FXEQ, FXDQ, FXMQ Models Method of Error Water leakage is detected based on float switch ON/OFF operation while the compressor is not in Detection operation. Error Decision When the float switch changes from ON to OFF while the compressor is not in operation.
SiUS371614E Troubleshooting by Error Code 3.15 Capacity Determination Device Abnormality Error Code Applicable All indoor unit models Models Method of Error Capacity is determined according to resistance of the capacity setting adaptor and the memory Detection inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is determined.
Troubleshooting by Error Code SiUS371614E 3.16 Transmission Abnormality between Indoor Unit PCB and Fan PCB Error Code Applicable FXMQ-PB Models Method of Error Transmission conditions between the indoor unit main PCB (A1P) and fan PCB (A2P) are checked via microcomputer. Detection Error Decision When normal transmission is not conducted for certain duration.
Page 207
SiUS371614E Troubleshooting by Error Code ∗1. Pull out and insert the connector once and check it is absolutely connected. Note: ∗2. Method to check transmission part of indoor unit main PCB. (1) Turn OFF the power and remove the connector X70A of indoor unit PCB (A1P). (2) Short circuit X70A.
Troubleshooting by Error Code SiUS371614E 3.17 Blower Motor Communication Error C1-07 Error Code Applicable FXTQ-TA Models Outline Error is issued if transmission abnormalities occur between indoor unit and fan motor. Error Decision If the response message from the fan motor is an abnormal message, and determined as such by Conditions the indoor unit, the indoor unit will execute a retry.
SiUS371614E Troubleshooting by Error Code 3.18 Thermistor Abnormality C4, C5, C9, CA Error Code Applicable C4, C5: All indoor units C9: except FXTQ-TA models Models CA: FXMQ-PB models only Method of Error The error is detected by temperature detected by thermistor. Detection Error Decision The thermistor becomes disconnected or shorted while the unit is running.
Troubleshooting by Error Code SiUS371614E 3.19 Combination Error between Indoor Unit PCB and Fan PCB Error Code Applicable FXMQ-PB Models Method of Error Check the condition of transmission with fan PCB (A2P) using indoor unit main PCB (A1P). Detection Error Decision When the communication data of fan PCB (A2P) is determined as incorrect.
SiUS371614E Troubleshooting by Error Code 3.20 Blower Motor HP Mismatch C6-01 Error Code Applicable FXTQ-TA Models Outline Error is issued if the manufacturer ID and output of the connected fan motor do not match those recognized by the indoor unit. Error Decision Gathers information on the manufacturer ID and output of the fan motor when initializing the fan Conditions...
Troubleshooting by Error Code SiUS371614E 3.21 Indoor Blower Does Not Have Required Parameters to Function C6-02 Error Code Applicable FXTQ-TA Models Outline Indoor units perform required settings for control on the fan motor, but if the minimum required settings are not made then information indicating as such will be included among the periodic control status information.
SiUS371614E Troubleshooting by Error Code 3.22 Remote Sensor Abnormality Error Code Applicable FXTQ-TA Models Method of Error The error is detected by remote sensor temperature. Detection Error Decision The remote sensor becomes disconnected or shorted while the unit is running. Conditions Supposed Defective indoor unit thermistor (R1T) for room temperature...
Troubleshooting by Error Code SiUS371614E 3.23 Humidity Sensor System Abnormality Error Code Applicable FXFQ Models Method of Error Even if an error occurs, operation still continues. Detection Error is detected according to the moisture (output voltage) detected by the moisture sensor. Error Decision When the moisture sensor is disconnected or short circuited Conditions...
SiUS371614E Troubleshooting by Error Code 3.24 Infrared Presence/Floor Sensor Error Error Code Applicable FXFQ-T, FXUQ-P Models Method of Error The contents of a failure vary with the detailed error code. Check the code and proceed with the Detection flowchart. Error Decision Error is detected based on sensor output signals Conditions Supposed...
Page 216
Troubleshooting by Error Code SiUS371614E Troubleshooting Diagnosis procedure 1 Infrared presence sensor error (Error code CE-01) Is the connection of the adaptor Connect the connector correctly. PCB connector X9A normal? (∗) Is the connection of the Connect the connector correctly. sensor connector normal? Check infrared presence sensor output;...
Page 217
SiUS371614E Troubleshooting by Error Code Troubleshooting Diagnosis procedure 2 Infrared floor sensor error (Error code CE-02) Is the connection of the adaptor Connect the connector correctly. PCB connector X9A normal? (∗) Is the connection of the Connect the connector correctly. sensor connector normal? Check infrared floor sensor output;...
Page 218
Troubleshooting by Error Code SiUS371614E Troubleshooting Diagnosis procedure 3 Infrared floor sensor error (Error code CE-03) Is the connection of the adaptor Connect the connector correctly. PCB connector X9A normal? (∗) Is the connection of the Connect the connector correctly. sensor connector normal? Check infrared floor sensor output;...
Page 219
SiUS371614E Troubleshooting by Error Code Troubleshooting Diagnosis procedure 4 Infrared floor sensor error (Error code CE-04) Is the connection of the adaptor Connect the connector correctly. PCB connector X9A normal? (∗) Is the connection of the Connect the connector correctly. sensor connector normal? Check infrared floor sensor output;...
Troubleshooting by Error Code SiUS371614E 3.25 Remote Controller Thermistor Abnormality Error Code Applicable All indoor unit models Models Method of Error Error detection is carried out by temperature detected by the remote controller thermistor. Detection Error Decision The remote controller thermistor becomes disconnected or shorted while the unit is running. Conditions Supposed Defective remote controller thermistor...
SiUS371614E Troubleshooting by Error Code 3.26 Outdoor Unit Main PCB Abnormality Error Code Applicable All outdoor unit models Models Method of Error Abnormality is detected under the communication conditions in the hardware section between the Detection indoor unit and outdoor unit. Error Decision When the communication conditions in the hardware section between the indoor unit and the Conditions...
Troubleshooting by Error Code SiUS371614E 3.27 Actuation of High Pressure Switch Error Code Applicable All outdoor unit models Models Method of Error Detect continuity across the high pressure switch in the protection device circuit. Detection Error Decision When part of the protection device circuit opens. Conditions (Reference) Operating pressure of the high pressure switch: Operating pressure: 4.0 MPa (580 psi)
Page 223
SiUS371614E Troubleshooting by Error Code Service Checker CHECK 12 Compare the high pressure value checked with the Service Checker and the actual value measured by pressure sensor (∗1). Check if the high pressure value and the actual value Replace the outdoor unit measured by main PCB (A1P).
Troubleshooting by Error Code SiUS371614E 3.28 Actuation of Low Pressure Sensor Error Code Applicable All outdoor unit models Models Method of Error Make judgement of pressure detected by the low pressure sensor with the outdoor unit main PCB. Detection Error Decision When low pressure caused a drop while the compressor is in operation: Operating pressure: 0.07 MPa (10.2 psi) Conditions...
SiUS371614E Troubleshooting by Error Code 3.29 Inverter Compressor Motor Lock Error Code Applicable All outdoor unit models Models Method of Error Outdoor unit PCB takes the position signal from UVW line connected between the inverter and compressor, and the error is detected when any abnormality is observed in the phase-current Detection waveform.
Page 226
Troubleshooting by Error Code SiUS371614E The insulation resistance of the relevant Replace the compressor. ( 1) compressor is low (< 100 kΩ) REYQ72TA: M1C REYQ96-168TA: M1C, M2C Power OFF The relevant compressor has a wiring disconnection in it. Restart the compressor, and then check for the Quit work.
SiUS371614E Troubleshooting by Error Code 3.30 Compressor Damage Alarm Error Code Applicable All outdoor unit models Models Method of Error Determine the symptom to be error by detecting the revolutions of the compressor and pressure Detection values detected by the high and low pressure sensors, and further making a comparison between a theoretical current value of the compressor calculated from parameters detected and an actual current value detected by the power transistor.
Page 228
Troubleshooting by Error Code SiUS371614E the high pressure and low pressure checked by the service checker the Replace the outdoor unit main same as the actual measured PCB (A1P). values of the high and low pressure sensors? CHECK 4 Replace the inverter PCB. Is the power transistor normal? REYQ72TA: A3P...
SiUS371614E Troubleshooting by Error Code 3.31 Outdoor Fan Motor Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to the value of current flowing through the inverter PCB (or fan PCB in case of Detection Fan Motor 2).
Page 230
Troubleshooting by Error Code SiUS371614E There is no continuity across the fuse Replace the fan PCB. ( 1) (F101U) on the fan PCB. REYQ72TA: A4P REYQ96-168TA: A4P, A7P fan cannot be rotated by hand Replace the relevant fan motor. when disconnecting the connector from the fan motor.
SiUS371614E Troubleshooting by Error Code 3.32 Electronic Expansion Valve Coil Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to whether or not there is continuity across the electronic expansion valve coils (Y1E-Y5E). Detection Error Decision When no current flows through common (COM[+]) at the time of turning ON the power supply.
Troubleshooting by Error Code SiUS371614E 3.33 Discharge Pipe Temperature Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to temperature detected with the discharge pipe or compressor body thermistor. Detection Error Decision When discharge pipe temperature becomes abnormally high (i.e., 135°C (275°F) or more) Conditions When discharge pipe temperature sharply rises (remains at 120°C (248°F) or more for a period of consecutive 10 minutes)
Page 233
SiUS371614E Troubleshooting by Error Code Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Connect the Service Checker. Reset the system operation, and then restart it. CHECK 11 Are the characteristics of the discharge pipe and Replace the relevant thermistor.
Troubleshooting by Error Code SiUS371614E 3.34 Wet Alarm Error Code Applicable All outdoor unit models Models Method of Error In cooling operation, detect the condition under which liquid refrigerant returns to the compressor, according to the temperature and pressure of each part. Detection Error Decision When the following wet state continues for a period of 90 minutes, an alert is issued.
SiUS371614E Troubleshooting by Error Code 3.35 Refrigerant Overcharged Error Code Applicable All outdoor unit models Models Method of Error Detect overcharged refrigerant according to outdoor air temperature, heat exchanger deicer Detection temperature, and liquid pipe temperature during check operation. Error Decision When the amount of refrigerant, which is calculated using outdoor air temperature, heat exchanger Conditions deicer temperature, and liquid pipe temperature during check operation, exceeds the regular...
Troubleshooting by Error Code SiUS371614E 3.36 Harness Abnormality (between Outdoor Unit Main PCB and Inverter PCB) Error Code Applicable All outdoor unit models Models Method of Error Check for the transmission conditions of the following jumpers between the PCB using Detection microcomputer: Between X28A (Outdoor unit main PCB) and X6A (Inverter PCB) (∗1)
SiUS371614E Troubleshooting by Error Code 3.37 Outdoor Fan Motor Signal Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect of abnormal signal from fan motor. Detection Error Decision An abnormal signal is detected at startup of the fan motor operation. Conditions Supposed Abnormal signal from fan motor (Circuit failure)
Troubleshooting by Error Code SiUS371614E 3.38 Thermistor Abnormality H9, J3, J5, J6, J7, J8, J9 Error Code Applicable All outdoor unit models Models Method of Error Detect according to temperature detected with individual thermistors. Detection Error Decision The system is in operation and the thermistor causes wiring disconnection or short circuit in it. Conditions Supposed Defective connection of thermistor...
Page 239
SiUS371614E Troubleshooting by Error Code ∗1. Error codes and thermistors Note: REYQ72TA REYQ96/120TA REYQ144/168TA Error Applicable Electric Electric Electric Code Thermistor Connector Connector Connector symbol symbol symbol Outdoor air X18A X18A X18A X19A Discharge (Group R21T R21T X19A pipe (M1C) connector) (Group X19A...
Troubleshooting by Error Code SiUS371614E 3.39 High Pressure Sensor Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to temperature detected with the high pressure sensor. Detection Error Decision The high pressure sensor is short circuit or open circuit. Conditions (Pressure range: 0-4.3 MPa (0-624 psi)) Supposed...
SiUS371614E Troubleshooting by Error Code 3.40 Low Pressure Sensor Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to temperature detected with the low pressure sensor. Detection Error Decision The low pressure sensor is short circuit or open circuit. Conditions (Pressure range: 0-1.7 MPa (0-247 psi)) Supposed...
Troubleshooting by Error Code SiUS371614E 3.41 Inverter PCB Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to current value detected during the output of waveform before compressor Detection startup Detect according to current value detected with the current sensor during synchronous operation for startup Error Decision When overcurrent (OCP) flows during the output of waveform...
Page 243
SiUS371614E Troubleshooting by Error Code Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Turn OFF the power supply once, and then turn it ON again. Return to normal? The error could have resulted from external factors other than failures (e.g.
Troubleshooting by Error Code SiUS371614E 3.42 Reactor Temperature Rise Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to the value detected with the reactor surface thermistor. Detection Error Decision When the temperature detected with the reactor surface thermistor is more than the specified Conditions temperature.
SiUS371614E Troubleshooting by Error Code 3.43 Inverter Radiation Fin Temperature Rise Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect temperature of power module of the inverter PCB. Detection Error Decision Thermistor located inside the power module of the inverter PCB for compressor and fan motor. Conditions Cooling tube plate poor heat-exchange.
Troubleshooting by Error Code SiUS371614E 3.44 Inverter Compressor Instantaneous Overcurrent Error Code Applicable All outdoor unit models Models Method of Error Detect current flowing through the power transistor. Detection Error Decision When instantaneously overcurrent flows through the power transistor. Conditions Supposed Defective compressor coil (such as wiring disconnection or insulation failure) Causes...
Page 247
SiUS371614E Troubleshooting by Error Code Power OFF insulation resistance of the relevant Replace the compressor is 100 kΩ compressor. ( 1) or less. REYQ72TA: M1C REYQ96-168TA: M1C, The coil of the relevant compressor has caused Replace the wiring disconnection compressor. ( 1) in it.
Troubleshooting by Error Code SiUS371614E 3.45 Inverter Compressor Overcurrent Error Code Applicable All outdoor unit models Models Method of Error Detect current flowing through the power transistor. Detection Error Decision When the secondary-side inverter current exceeds. Conditions Supposed Compressor overloaded Causes Wiring disconnection in compressor coil Disconnection of compressor wiring...
Page 249
SiUS371614E Troubleshooting by Error Code Power OFF insulation resistance of the Replace the relevant compressor is compressor. ( 1) 1 MΩ or less to ground. REYQ72TA: M1C REYQ96-168TA: M1C, The coil of the relevant compressor has caused Replace the wiring disconnection compressor.
Troubleshooting by Error Code SiUS371614E 3.46 Inverter Compressor Startup Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect error according to the signal waveform of compressor. Detection Error Decision When compressor startup operation has not been completed. Conditions Supposed The stop valve is not opened...
Page 251
SiUS371614E Troubleshooting by Error Code Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Startup for the first time after installation? Is a proper amount of refrigerant Charge a proper amount of charged? refrigerant.
Page 252
Troubleshooting by Error Code SiUS371614E Refrigerant is melting (No power Eliminate the melting state of applied for a period of 6 refrigerant. hours or more) Is the insulation resistance of the Replace the compressor. ( 1) relevant compressor 100 kΩ or REYQ72TA: M1C more? REYQ96-168TA: M1C, M2C...
SiUS371614E Troubleshooting by Error Code 3.47 Transmission Error between Inverter PCB and Outdoor Unit Main PCB Error Code Applicable All outdoor unit models Models Method of Error Check for the transmission conditions between the inverter PCB and the outdoor unit main PCB Detection using a microcomputer.
Page 254
Troubleshooting by Error Code SiUS371614E microcomputer normal monitor indication This is not the LC error. lamp (green) on the outdoor unit main PCB (A1P) Recheck the error code. is blinking. microcomputer The fuse of normal monitor indication Replace the inverter PCB. the noise filter PCB has lamp (green) on the outdoor REYQ72TA: A3P...
SiUS371614E Troubleshooting by Error Code 3.48 Power Supply Voltage Imbalance Error Code Applicable All outdoor unit models Models Method of Error Detect voltage imbalance through PCB. Detection Error Decision When power supply voltage imbalance exceeds approximately 12 V. Conditions Error is not decided while the unit operation is continued. P1 will be displayed by pressing the inspection button.
Page 256
Explanation to users Be sure to explain user that “power supply Hand the “Notice of Inspection Results” to user to ask voltage imbalance” will occur and Daikin him/her to rectify the imbalance. accepts no responsibility for the imbalance. ∗1. Make measurement of voltage at the power supply terminal block (X1M).
SiUS371614E Troubleshooting by Error Code 3.49 Reactor Temperature Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect according to the value detected with the reactor surface thermistor. Detection Error Decision The system is in operation and the thermistor causes wiring disconnection or short circuit in it. Conditions Supposed Defective connection of thermistor...
Troubleshooting by Error Code SiUS371614E 3.50 Inverter Radiation Fin Temperature Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect the resistance of the following thermistors during the compressor stops running: Detection Radiation fin thermistor Thermistor located in PCB circuit Error Decision When the resistance of the thermistor comes to a value equivalent to open or short circuit.
SiUS371614E Troubleshooting by Error Code 3.51 Field Setting after Replacing Outdoor Unit Main PCB Abnormality or Combination of PCB Abnormality Error Code Applicable All outdoor unit models Models Method of Error This error is detected according to communications with the inverter PCB. Detection Error Decision Make judgement according to communication data on whether or not the type of the inverter PCB is...
Troubleshooting by Error Code SiUS371614E 3.52 Refrigerant Shortage Error Code Applicable All outdoor unit models Models Method of Error Detect refrigerant shortage according to a low pressure level or a difference in heat exchanging Detection temperature from the suction pipe. Error Decision Low pressure becomes 0.1 MPa (14.5 psi) or less.
SiUS371614E Troubleshooting by Error Code 3.53 Reverse Phase, Open Phase Error Code Applicable All outdoor unit models Models Method of Error The phase of each phase are detected by reverse phase detection circuit and right phase or Detection reverse phase are judged. Error Decision When a power supply is reverse phase, or T phase is open phase.
Troubleshooting by Error Code SiUS371614E 3.54 Power Supply Insufficient or Instantaneous Abnormality Error Code Applicable All outdoor unit models Models Method of Error Detect the voltage of capacitor of the main circuit in the inverter PCB. Detection Error Decision When the voltage in the DC circuit (between diode module and power module) falls below 380VDC. Conditions Supposed Abnormal power supply voltage...
Page 263
SiUS371614E Troubleshooting by Error Code The insulation resistance of the fan Replace the fan motor. motor is not more than If the motor gets severely 1 MΩ. damaged, the inverter PCB ( 1) should also be replaced. REYQ72TA: M1C REYQ96-168TA: M1C, M2C CHECK 4 Is the power Replace the inverter PCB.
Troubleshooting by Error Code SiUS371614E 3.55 Check Operation not Executed Error Code Applicable All outdoor unit models Models Method of Error Check operation is executed or not executed Detection Error Decision Error is decided when the unit starts operation without check operation. Conditions Supposed Check operation is not executed.
SiUS371614E Troubleshooting by Error Code 3.56 Transmission Error between Indoor Units and Outdoor Units Error Code Applicable All indoor unit models All outdoor unit models Models Method of Error Microcomputer checks if transmission between indoor and outdoor units is normal. Detection Error Decision When transmission is not carried out normally for a certain amount of time...
Page 266
Troubleshooting by Error Code SiUS371614E Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check for details of error in monitor mode. U4-01 Refer to troubleshooting U4-03 (Indoor unit system transmission error) Has the indoor or...
Page 267
SiUS371614E Troubleshooting by Error Code U4-03 Indication after launch test Check controller indoor units : operation? (1) Some error about thermistor, or fan motor, electronic expansion valve, or defective PCB. (2) Test operation was interrupted by button BS1 Operate all indoor units. "Mode".
Troubleshooting by Error Code SiUS371614E 3.57 Transmission Error between Remote Controller and Indoor Unit Error Code Applicable All indoor unit models Models Method of Error Microcomputer checks if transmission between indoor unit and remote controller is normal. Detection Error Decision Transmission is not carried out normally for a certain amount of time.
SiUS371614E Troubleshooting by Error Code 3.58 Transmission Error between Outdoor Units Error Code Applicable All outdoor unit models Models Method of Error Microcomputer checks if transmission between outdoor units is normal. Detection Error Decision When transmission is not carried out normally for a certain amount of time Conditions Supposed Connection error of transmission wirings between outdoor unit and external control adaptor for...
Page 270
Troubleshooting by Error Code SiUS371614E Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Ensure the sub code or the lamp display of monitor mode, and then go to the following: U7-01 Error code Sub code...
Page 271
SiUS371614E Troubleshooting by Error Code Diagnosis Flowchart-1 U7-01 Error code Sub code (Transmission error when the external control adaptor is mounted) there any wiring disconnection or wiring error in the transmission Modify the transmission wirings wirings to the external to the external control adaptor for control adaptor for outdoor unit.
Page 272
Troubleshooting by Error Code SiUS371614E Diagnosis Flowchart-2 U7-02 Error code Sub code (Transmission error when the external control adaptor for outdoor unit is mounted) Unified Cool/ Heat Set Cool/Heat selection selection for the external control adaptor for outdoor unit to “IND.” Cool/Heat selection for the external control adaptor...
Page 273
SiUS371614E Troubleshooting by Error Code Diagnosis Flowchart-3 U7-03 Error code Sub code (Transmission error between master and slave 1) multi transmission wirings to multi slave 1 have Replace the outdoor unit main caused wiring disconnection in them or are being PCB for multi slave 1.
Page 274
Troubleshooting by Error Code SiUS371614E Diagnosis Flowchart-6 U7-06 Error code Sub code (Manual address setting error for slave 1, 2) One of outdoor unit multi transmission wirings has Replace the outdoor unit main caused wiring disconnection in it PCB (A1P). or been disconnected.
SiUS371614E Troubleshooting by Error Code 3.59 Transmission Error between Main and Sub Remote Controllers Error Code Applicable All indoor unit models Models Method of Error In case of controlling with 2 remote controller, check the system using microcomputer if signal Detection transmission between indoor unit and remote controller (main and sub remote controller) is normal.
Troubleshooting by Error Code SiUS371614E 3.60 Transmission Error between Indoor Unit and Outdoor Unit in the Same System Error Code Applicable All indoor unit models All outdoor unit models Models Method of Error Detect the error signal for the other indoor unit within the circuit by outdoor unit PCB. Detection Error Decision The error decision is made on any other indoor unit within the system concerned...
SiUS371614E Troubleshooting by Error Code 3.61 Improper Combination of Indoor Unit and Outdoor Unit, Indoor Unit and Remote Controller Error Code Applicable All indoor unit models All outdoor unit models Models Method of Error A difference occurs in data by the type of refrigerant between indoor and outdoor units. Detection The number of indoor units connected is out of the allowable range.
Page 278
Troubleshooting by Error Code SiUS371614E Diagnosis Flowchart-1 UA-17 Error code Sub code number of indoor Is the units connected to the model of indoor Replace the outdoor unit main same system is not unit FXTQ? PCB (A1P). more than 64. Incorrect electric heater capacity setting...
Page 279
SiUS371614E Troubleshooting by Error Code Diagnosis Flowchart-3 UA-20 Error code Sub code Multi connection? Replace the outdoor unit main PCB (A1P). Was the different model outdoor unit PCB Replace the outdoor unit main PCB of outdoor unit is replaced with a spare (A1P).
Page 280
Troubleshooting by Error Code SiUS371614E Diagnosis Flowchart-5 UA-31 Error code Sub code Is the multi combination of Correct the multi combination of outdoor units outdoor units. proper? Was the outdoor unit PCB Replace the outdoor unit main PCB replaced with a spare (A1P).
SiUS371614E Troubleshooting by Error Code 3.62 Incorrect Electric Heater Capacity Setting UA-17 Error Code Applicable FXTQ-TA Models Outline After attaching optional electric heater, if the electric heater capacity setting (11(21)-5) is made mistakenly for heaters not featured in the lineup, heating via unintended levels of airflow will be prevented.
Troubleshooting by Error Code SiUS371614E 3.63 Address Duplication of Centralized Controller Error Code Applicable All indoor unit models Models Centralized controller Method of Error The principal indoor unit detects the same address as that of its own on any other indoor unit. Detection Error Decision The error decision is made as soon as the abnormality aforementioned is detected.
SiUS371614E Troubleshooting by Error Code 3.64 Transmission Error between Centralized Controller and Indoor Unit Error Code Applicable All indoor unit models Schedule timer Central remote controller Models Method of Error Microcomputer checks if transmission between indoor unit and centralized controller is normal. Detection Error Decision When transmission is not carried out normally for a certain amount of time...
Page 284
Troubleshooting by Error Code SiUS371614E Check transmission wiring between centralized controller for Correct the wiring. any broken wire. CHECK 15 Check the transmission wiring between main centralized controller for any Correct the wiring. broken wire. CHECK 15 the main centralized controller Correct the connection of the setting connector been connector.
SiUS371614E Troubleshooting by Error Code 3.65 System not Set yet Error Code Applicable All indoor unit models Models All outdoor unit models Method of Error On check operation, the number of indoor units in terms of transmission is not corresponding to that Detection of indoor units that have made changes in temperature.
Troubleshooting by Error Code SiUS371614E 3.66 System Abnormality, Refrigerant System Address Undefined Error Code Applicable All indoor unit models All outdoor unit models Models Method of Error Detect an indoor unit with no auto address setting. Detection Error Decision The error decision is made as soon as the abnormality aforementioned is detected. Conditions Supposed Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor...
Page 287
SiUS371614E Troubleshooting by Error Code Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Does an error electricity occur even after being introduce 12 minutes elapses for the first time after from the time when Normal installation or after an...
Check SiUS371614E 4. Check High Pressure Check CHECK 1 Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points. ←Check to be sure the stop valve is open. Stop valve closed Local High pipe ←Conduct visual checks for pipe conditions. pressure Bent or crashed pipe resistance...
SiUS371614E Check Low Pressure Check CHECK 2 Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points. [In cooling] Defective low pressure ←Is the pressure value checked with the Service Checker sensor Defective (∗1.) corresponding to the measurement value of the pressure sensor? compressor Defective ←Are the voltage characteristics normal?
Check SiUS371614E Superheat Operation Check CHECK 3 Identify the defective points referring to the failure factor analysis (FTA) as follows. Hot gas circuit clogging Defective hot Defective solenoid ← Are the coil resistance and insulation normal? gas bypass valve coil control Defective solenoid valve body...
SiUS371614E Check Power Transistor Check CHECK 4 Perform the following procedures prior to check. (1) Power OFF. (2) Remove all the wiring connected to the PCB where power transistors are mounted on. Preparation ∗ Prepare the analog type of multimeter. Multimeter For the digital type of multimeter, those with diode check function are available for the...
Check SiUS371614E Refrigerant Overcharge Check CHECK 6 In case of VRV Systems, the only way to judge as the overcharge of refrigerant is with operating conditions due to the relationship to pressure control and electronic expansion valve control. As information for making a judgement, refer to the information below. Diagnosis of overcharge of refrigerant 1.
SiUS371614E Check Refrigerant Shortage Check CHECK 7 In case of VRV Systems, the only way to judge as the shortage of refrigerant is with operating conditions due to the relationship to pressure control and electronic expansion valve control. As information for making a judgement, refer to the information below. Diagnosis of shortage of refrigerant 1.
Check SiUS371614E Vacuuming and Dehydration Procedure CHECK 8 Conduct vacuuming and dehydration in the piping system following the procedure for <Normal vacuuming and dehydration> described below. Furthermore, if moisture may get mixed in the piping system, follow the procedure for <Special vacuuming and dehydration>...
SiUS371614E Check Thermistor Check CHECK 11 Thermistor type of indoor units Indoor heat exchanger Indoor heat exchanger Suction air thermistor Discharge air thermistor (liquid) thermistor (gas) thermistor Model FXFQ-T Type C – FXFQ-P Type D – FXZQ-M Type B – FXUQ-P Type C –...
Page 296
Check SiUS371614E Table 2 Thermistor temperature Resistance (kΩ) (°C) (°F) Type A Type B Type C Type D –30 –22 363.8 361.7719 – 336.7 –25 –13 266.8 265.4704 – 253.1 –20 –4 197.8 196.9198 – 191.2 –15 148.2 147.5687 – 144.1 –10 112.0...
Page 297
SiUS371614E Check Thermistor temperature Resistance (kΩ) (°C) (°F) Type E Type H Type J –30 –22 362.4862 3257.371 359.8518 –25 –13 265.9943 2429.222 265.0699 –20 –4 197.3083 1827.883 197.1476 –15 147.8597 1387.099 147.7348 –10 111.8780 1061.098 111.7984 –5 85.4291 817.9329 85.3927 65.8000 635.0831...
SiUS371614E Check 4.10 Broken Wire Check of the Relay Wires CHECK 15 1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires On the system shown below, turn OFF the power supply to all equipment, short circuit between the outdoor-outdoor unit terminal F1 and F2 in the "Outdoor Unit A" that is farthest from the central remote controller, and then conduct continuity checks between the transmission wiring terminal blocks F1 and F2 of the central remote controller using a multimeter.
Check SiUS371614E 4.11 Fan Motor Connector Check (Power Supply Cable) CHECK 16 (1) Turn OFF the power supply. Measure the resistance between phases of U, V, W at the motor side connectors (3-core wire) to check that the values are balanced and there is no short circuiting, while connector or relay connector is disconnected.
SiUS371614E Check 4.13 Electronic Expansion Valve Coil Check CHECK 18 Remove the connector for electronic expansion valve (X7A) from PCB. Measure the resistance value between pins and check the continuity to judge the condition. 1) White White (1) 2) Yellow φ1 Red (5) φ3...
Page 323
Revision History Month / Year Version Revised contents 02 / 2017 SiUS371614E First edition...
Page 324
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.