SiUS371614E
∗1. Make a comparison between voltage measured by the pressure sensor and that read by the
Note:
CHECK 1
CHECK 12
Service Diagnosis
A
Service Checker
CHECK 12
Compare the high pressure value checked with the Service Checker and
the actual value measured by pressure sensor (∗1).
Check
if the high
pressure value and
the actual value
measured by
pressure sensor
are the
same.
YES
-The high pressure sensor is normal, and pressure detection with the outdoor
unit main PCB is also normal.
-The high pressure has really become high.
CHECK 1
: Eliminate factors that cause the high pressure to rise.
pressure gauge.
(The pressure sensor makes measurement of voltage at its connector block to convert it to
pressure.
)
CHECK 12
Refer to page 275.
Refer to page 285.
NO
Troubleshooting by Error Code
Replace the outdoor unit
main PCB (A1P).
210