Service Diagnosis
U4-03
Indication after
launch test
operation?
NO
Operate all indoor units.
Do all units display U9?
YES
Did 2 minutes or more
elapse after
U9
is
displayed?
YES
YES
NO
NO
Troubleshooting by Error Code
Check controller indoor units :
(1) Some error about
thermistor, or fan motor,
electronic expansion
valve, or defective PCB.
(2) Test operation was
interrupted by button BS1
"Mode".
Check all indoor error
indication.
Carry out the diagnosis again
after a lapse of 2 minutes or
more.
The PCB of indoor units
displaying U9 are normal.
Check for indoor units of
other systems to troubleshoot
them according to relevant
error codes.
254