Daikin REYQ-TA Series Service Manual page 217

Heat recovery 60 hz
Table of Contents

Advertisement

SiUS371614E
Troubleshooting
Service Diagnosis
Diagnosis procedure 2
Infrared floor sensor error
(Error code CE-02)
Is the
connection of the adaptor
PCB connector X9A
normal? (∗)
YES
Is the
connection of the
sensor connector
normal?
YES
Check infrared floor sensor output; refer to sensor
and address data No. 26.
Displays
"--" by the above
verification
method.
YES
Turn off the power and then reconnect.
Displays CE-02
again or "--" for
sensor and
address data.
YES
∗ Check whether A2P connector is well connected or not.
Troubleshooting by Error Code
NO
Connect the connector correctly.
NO
Connect the connector correctly.
NO
Normal.
NO
Normal.
Replace the sensor.