D9412G/D7412G | Operation & Installation Guide |
Using D8129 OctoRelays and D8128D
OctoPOPITs together on the same ZONEX
Terminals is limited and depends on the
number of D8128D OctoPOPITs and
D81289 OctoRelays connected to a single
ZONEX Bus.
Refer to Table 16 for information on the
maximum number of D8128Ds and D8129s
that can be connected to a single ZONEX
Bus.

Table 16: Number of D8128Ds Used with D8129s

If the Number of
D8128Ds Connected to a
Single Zonex Bus Is:
9
10
11
12
13
14
9.2

D811 Arm Status Relay Module

The D811 Arm Status Relay Module allows the addition
of a single off-board relay output to the system. Alarm
output, auxiliary relay, sensor reset, arming status, point
status, alarm memory, or remote functions can be
assigned to the D811 relay output. It is not restricted to
the Arming Status Mode only.
Relay Numbers for D811 Not Programmable: If the
D811 is connected to ZONEX 1, Terminal 28, use relay
number 53 for the relay output. If the D811 is connected
to ZONEX 2, Terminal 26 on the D9412G, use relay
number 117 for the relay output.
D811 Modules connect as shown in Figure 24 and Figure
25. Review Section 5.0 Power Outputs to ensure enough
power is provided for the powered devices that will be
connected to the system. See Relay Parameters in the
D9412G/D7412G Program Entry Guide for programming
details.
D811 Restricted for Fire Systems: The D811 relay
output is not supervised and cannot be used in fire or
combined fire/burglary installations for primary
indication devices.
9.2. 1

Relay Output

Bosch Security Systems | 10/03 | 43488E
9.0 Off-Board Relays
Do Not Connect More
Than this Number of
D8129s:
6
5
4
3
1
1
Each D811 relay output provides a Form C dry contact
rated for 1.0 A at 12 VDC. Normally-open, common,
and normally-closed terminals are available. When an
individual output is activated, there is continuity
between the normally-open and common terminals.
When the output is not activated, there is continuity
between the normally-closed and common terminals.
Relay outputs can activate while
programming the panel. Disconnect
equipment connected to relay outputs while
performing these functions.
9.2.2

Installation

Install the D811 in the enclosure with the panel (see
Figure 2) or in an adjacent enclosure no more than 1.5 m
(5 ft.) from the panel. Use 1.5 mm (16 AWG) to 0.8 mm
(22 AWG) wire.
To install D811 Modules in the enclosure with the panel:
1. Align the D811 Module with any of the four
mounting locations in the enclosure. See Figure 2.
2. Using the screws provided with the module, secure
it in the enclosure.
Use the D137 Mounting Bracket or D9002
Mounting Skirt to install D811 Modules in
enclosures with no module available mounting
locations.
9.2.3

Wiring Connections

Power down the panel to connect D811 Modules as
shown in Figure 24 and Figure 25. Note that the D811 for
relay number 53 connects to ZONEX 1. The D811 for
relay number 117 connects to ZONEX 2 on the
D9412G.
EN | 51