4.0 Power Supply; Replacing The Battery; Figure 5: Non-Power Limited Wiring - Bosch D9412G Operations & Installation Manual

Table of Contents

Advertisement

D9412G/D7412G | Operation & Installation Guide |

Figure 5: Non-Power Limited Wiring

1
3
1 - Only required if external batteries are used.
2 - Battery wires
3 - 6.4 mm (0.25 in.) minimum. To ensure proper
spacing, secure wires using Tie-Wraps or
similiar devices.
4.2.3

Replacing the Battery

Replace batteries every 3 to 5 years under normal use.
Record the date of installation directly on the battery.
Exceeding the maximum output ratings or
installing the transformer in an outlet that is
routinely switched off causes heavy discharges.
Routine heavy discharges can lead to premature
battery failure.
D8132 Boost Battery Backup: Adding a D8132 Battery
Charger Module supports additional batteries of up to
27 Ah capacity, if required.
The D8132 Battery Charger Module can be used to
connect two additional batteries for a total of four. The
Bosch Security Systems | 10/03 | 43488E

4.0 Power Supply

2
1
2
D
+ AUX
3
BATTERY NEGATI
4
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
5
PROGRAMMABLE
RELAY A
6
ALARM OUTPUTS
Terminals
7
RELAY B
7
Requires Optional
4
D136 Relay
In ALT ALARM
RELAY C
8
& SW AUX
9
COMMON
10
EARTH GROUND
GROUND FAULT DETECT
Enabled
Disabled
GROUND START
GROUND START
Requires
Relay # D136 in
Ground
Start Socket
6
&
8
Point 1 Point 2
LOOP START
GND START
PHONE
RED
LED
11
12
13
ON WHEN
COMMUNICATING
OFF WHEN IDLE
4 - Option wires
5 - Output or zone wires
6 - Standby battery
panel plus any connected D8132 Modules and AUX
power supplies must be on the same AC circuit to
discharge evenly if AC power fails. The number of
D8132 Modules is determined by the number of
available outlets on the same circuit. Refer to the
Standby Battery and Current Rating Chart in the
D9412G/D7412G Approved Applications Compliance Guide
for battery standby time calculations.
In applications where the supervision of two
batteries is required by the AHJ, use a D113
Battery Supervision Module.
5