ESIE09-08B
Caution
Capacity Setting after changing the main indoor PC Board (A1P) to spare parts PC Board
When you change the main indoor PC Board (A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X23A.
(See Below)
Capacity Setting Adapter
Test Operation
Capacity Class
1
CAPACITY SETTING ADAPTER (for 011/J112)
011 (112)
2
014 (140)
CAPACITY SETTING ADAPTER (for 014/J140)
3
016 (160)
CAPACITY SETTING ADAPTER (for 016/J160)
Note
Field Setting
X23A
107