Daikin ALTHERMA HT Service Manual page 115

Hide thumbs Also See for ALTHERMA HT:
Table of Contents

Advertisement

ESIE09-08B
[C] Leaving water temperature limits
First
code
C
To prevent misuse concerning leaving water temperatures, it is possible to limit the set points.
 [C-00] Set point: leaving water maximum temperature
 [C-01] Set point: leaving water minimum temperature
Test Operation
Second
code
Setting name
Leaving water temperature limits
00
Set point: leaving water maximum
temperature
01
Set point: leaving water minimum
temperature
Field Setting
Default
value
Range
Step
80
37~80
1
25
25~37
1
Unit
°C
°C