Daikin ALTHERMA HT Service Manual page 105

Hide thumbs Also See for ALTHERMA HT:
Table of Contents

Advertisement

ESIE09-08B
[4] Disinfection function
First
code
4
This mode will disinfect the domestic hot water tank by periodically heating the domestic water
to a specific temperature.
If a domestic hot water tank is installed, the disinfection function is enabled by default.
Note :
 [4-00] Status: defines whether the disinfection function is turned ON (1) or OFF (0).
 [4-01] Operation interval: day of the week at which the domestic water should be heated.
 [4-02] Start time: time at which the disinfection operation is started.
Even if all schedule timers are de-activated and there is no reheat function active, the
disinfection function will operate if a domestic hot water tank is installed and field setting [4-00]
is set to ON.
The disinfection function field settings must be configured by the installer according to national
and local regulations.
Refer to "[5] Automatic setback and disinfection set point" on page 94 for temperature set
points.
This function may be disabled if the set point storage temperature is higher than the disinfection
Note :
set point.
Test Operation
Second
code
Setting name
Disinfection function
00
Status: disinfection operation
01
Disinfection operation day selection
02
Disinfection operation start time
Field Setting
Default
value
Range
Step
1 (ON)
0/1
Fri
Mon~Sun
23:00
0:00~23:00
1:00
Unit
hour
93

Advertisement

Table of Contents
loading

Table of Contents