ESIE09-08B
Method 2
During operation
When pushing the y button
When pushing the r/p button The schedule timer for space heating and domestic water heating along with
Operation example: Schedule timer based on ON/OFF instruction.
When setback function is enabled, the setback operation will have priority over the scheduled
action in the schedule timer if ON instruction is active. If OFF instruction is active this will have
priority over the setback function. At any time the OFF instruction will have the highest priority.
1
2
3
Test Operation
ON
OFF
B
22°C
22 22°C
65°C
65 65°C
19°C
19 19°C
62 62°C
62°C
0:30
16:00
18 18°C
18°C
60°C
60 60°C
23:00
23:00
23:00
A
ON
OFF
B
22°C
22 22°C
65°C
65 65°C
19 19°C
19°C
18°C
18 18°C
62 62°C
62°C
60°C
60 60°C
23:00
16:00
Schedule timer
1
Setback function
2
When both setback function and schedule timer are enabled
3
Setback function
A
ON/OFF instruction
B
Time
t
Temperature set point
T
Room temperature
Leaving water temperature
Space heating based on ON/OFF instruction
When the schedule timer switches space heating OFF, the controller will be
switched off (operation LED will stop working). Note that this has no influence
on the domestic water heating.
The schedule timer for space heating will stop (when active at that moment)
and will start again at the next scheduled ON function.
The "last" programmed command overrules the "preceding" programmed
command and will remain active until the "next" programmed command
occurs.
Example: imagine the actual time is 17:30 and actions are programmed at
13:00, 16:00 and 19:00. The "last" programmed command (16:00) overruled
the "previous" programmed command (13:00) and will remain active until the
"next" programmed command (19:00) occurs.
So in order to know the actual setting, one should consult the last programmed
command. It is clear that the "last" programmed command may date from the
day before. Refer to the operation manual.
The controller will be switched off (operation LED will stop working).
However the schedule timer icon will stay displayed which means that the
domestic heating stays enabled.
the quiet mode will be stopped and will not start again.
The schedule timer icon will not be displayed anymore.
ON
21°C
21 21°C
64°C
64 64°C
19 19°C
19°C
62 62°C
62°C
t
6:30
9:00
t
5:00
5:00
5:00
ON
21 21°C
21°C
64°C
64 64°C
19°C
19 19°C
62°C
62 62°C
t
6:30
9:00
Field Setting
89