Mitsubishi MELSEC-Q series Programming Manual page 60

Process control instructions
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

S.IN
(3) Engineering value reverse conversion
The result (T1) of the input limiter is converted reversely from the engineering value according to the following
expression.
T2
(EMAX EMIN)
(4) Digital filter
The input value (E1) is digitally filtered according to the following expression.
The digital filter is used to reduce noise.
BW=T2 +
× (Previous BW value - T2)
(5) Loop stop processing
(a) Setting 1 in SPA of the alarm detection (ALM) selects a loop stop.
A loop stop performs the following processing and terminates the S.IN instruction.
1) BW retains the last value.
2) SEA of the alarm detection (ALM) are turned to 0.
3) The operation mode (MODE) is changed to MAN.
4) BB1 to BB3 of BB are turned to 0.
(b) Setting 0 in SPA of the alarm detection (ALM) selects a loop run.
A loop run performs "(1) Range check".
Operation Error
In the following cases, the error flag (SM0) turns ON and the error code is stored in SD0.
Error code
When an operation error occurs
When the values of
4100
non-normalized number
When HH < H, L < LL, or NMAX < NMIN
When the values of
4140
non-normalized number
4141
When an operation error occurs
58
T1
NMIN
EMIN
NMAX
NMIN
Error definition
,
,
,
are either a non-numeric or
S1
D1
S2
D2
,
,
,
are either a non-numeric or
S1
D1
S2
D2
T2
EMAX
EMIN
NMIN
QnPHCPU
QnPRHCPU
––
––
NMAX
T1
QnUDPVCPU
––
––
––
––