Controller Resetting (Following
System Shutdown or Warning)
Use the following procedure to restart the generator set
after a system shutdown or to clear a warning lamp
condition. This procedure includes the resetting of the
optional remote annunciator.
Refer to Section 2.4.3, Emergency Stop Switch Reset
Procedure, to reset the generator set after an
emergency stop.
1. Disconnect the generator set load using the line
circuit breaker or automatic transfer switch.
2. Correct the cause of the fault shutdown or warning.
See the Safety Precautions and Instructions
section of this manual before proceeding.
3. Start the generator set by pressing the generator
set master control OFF/RESET button and then
press the RUN button.
When equipped, the remote annunciator alarm
horn sounds. Press the ALARM SILENCE/LAMP
TEST button to stop the alarm horn. The lamp
turns off.
4. Test operate the generator set to verify correction
of the shutdown cause.
5. Press
the
generator
OFF/RESET button to stop the generator set.
6. Press the generator set master control AUTO
button.
7. Reconnect the generator set load via the line circuit
breaker or automatic transfer switch.
2.4.9
Powering Up the Engine Control
Module (ECM)
Adapted from Service Bulletin SB-724 10/12.
The Decision-Makerr 3000 controller (with firmware
version 3.10 and higher) and the APM402 controller
have the capability to power up the engine ECM. On
generator sets with John Deere engines, the engine
ECM power-up feature allows service technicians to
access fault codes and other troubleshooting data using
their John Deere Diagnostic tools without the need to
start the generator set. Refer to Procedure for Powering
Up the Engine ECM on the following pages.
If the Decision-Makerr 3000 generator set controller
has a firmware version earlier than 3.10, there are two
TP-6694 7/18
set
master
control
ways to power up the engine ECM without starting the
generator set:
Use SiteTecht to power up the engine ECM. Refer
D
to Procedure for Powering Up the Engine ECM using
SiteTecht for Firmware Versions Before 3.10
following.
Update the firmware to version 3.10 or higher using a
D
PC with SiteTecht software and access Tech Tools
for the firmware update. Refer to the SiteTecht
Software Operation Manual TP-6701 as needed.
Use the following information to determine the controller
firmware version and perform the engine ECM power up
procedure.
Procedure for Checking the Firmware Version
1. Confirm that a fully charged battery is connected to
the generator set.
2. Press the generator set controller OFF/RESET
key.
3. Momentarily press the selector dial to activate the
digital display if dark.
4. Rotate the selector dial counterclockwise to
navigate through the main menus to the Overview
Menu as shown in Figure 2-8.
Overview
---->
##.# hr
Figure 2-8 Overview Menu
5. Press the selector dial at the Overview Menu in
order to access the Overview submenus.
6. Rotate the selector dial clockwise to navigate to the
(firmware) SW Version submenu as shown in
Figure 2-9.
SW Version:
3.10
Figure 2-9 SW Version Submenu
7. For Decision-Makerr 3000 controllers, if the
firmware version is earlier than 3.10, go to the
Procedure for Powering Up the Engine ECM using
SiteTecht. For Decision-Makerr 3000 controllers
with firmware version 3.10 or higher, or for APM402
controllers, continue to Procedure for Powering Up
the Engine ECM.