connected and then removed. (DEC3000 version 4.11
or higher, and APM402)
Engine Run Time displays the total run time hours.
Software Version displays in the Overview menu. Use
the version number to determine if an upgrade is
needed and/or when troubleshooting the controller.
Engine Metering Menu
Note: The Engine Metering Menu may vary depending
upon if the selector dial is rotated clockwise or
counterclockwise.
Engine Speed (Tachometer) displays the engine
speed in RPM.
Oil Pressure displays the engine oil pressure. This
value also shows in the Overview Menu.
Coolant Temperature displays the engine coolant
temperature. This value also shows in the Overview
Menu.
Fuel Level % displays the fuel tank level for diesel-
powered models if so equipped. This value also shows
in the Overview Menu.
Battery displays the DC voltage of the engine starting
battery(ies). This value also shows in the Overview
Menu.
Fuel Pressure displays fuel pressure for some engines.
Refer to the Appendix, Controller Displays from the
Engine ECM. This value also shows in the Overview
Menu.
Generator Metering Menu
Total Power kVA and kW displays alternator output as
actual output values.
Rated Power displays alternator output as a
percentage of the entered data value.
Volts displays the alternator output AC voltages. The
display shows all line-to-line and line-to-neutral voltage
combinations
for
three-phase
configurations.
Current displays the alternator output AC amps. The
display shows each line (L1-L2-L3) of three-phase
models or L1-L2 current for single-phase models.
Frequency (Hz) value displays for the output AC
voltage. This value also shows in the Overview Menu.
Reset Calibration providing the means to reset the
configuration values is available in this menu.
TP-6694 7/18
The calibration values are reviewable at all times and
provide the calibration of the voltage and current
sensing logic. Changing the system voltage or replacing
the circuit board requires a calibration adjustment.
To enable calibration, start the generator set and select
the Volts L1-L2 display.
pushbutton/rotary selector dial until the Calibration
Enabled popup appears. Calibration of each display is
now available. The display will show the following
values for three-phase generator sets. Single-phase
generator sets will only display items marked (*).
D
D
D
D
D
D
D
D
D
The user can change individual values or can select
Reset Calib?- -Yes to reset all values. The Reset Calib?
display will only show if calibration is enabled. Refer to
the requirements shown with Generator Set Calibration
in 2.4.7 Status and Notice Digital Displays.
To disable calibration, Rotate the pushbutton/rotary
selector dial until the <- -Return popup appears.
Momentarily press the pushbutton/rotary selector dial.
Stop the generator set if not already done.
Generator Set Information Menu
GenSet M/N displays the generator set model number.
GenSet S/N displays the generator set serial number.
Controller S/N displays the controller serial number.
Generator Set Run Time Menu
Engine Run Time displays the total run time hours.
This value also shows in the Overview Menu.
or
single-phase
Engine Loaded displays the total loaded hours.
Engine Starts displays the total number of generator
set startup events.
Total Energy displays the total kW hours.
Volts L1-L2 *
Volts L2-L3
Volts L3-L1
Volts L1-N *
Volts L2-N *
Volts L3-N
Current L1 *
Current L2 *
Current L3
Section 1 Specifications and Features