2.3.5
Resetting
the Controller
after a
Fault Shutdown
Always
identify
and correct
the
cause of a fault
shutdown
before
resetting the controller.
Use the
following procedure to reset the generator set controller
after a fault shutdown.
1. Move
the
generator
set
master
switch
to
OFF/RESET.
2. Disconnect the generator set from the load using
the line circuit breaker or ATS.
See the safety
precautions at the beginning of this section before
proceeding.
3. Identify
and
correct
the
cause
of the
fault
shutdown.
See the safety precautions
at the
beginning of this section before proceeding.
Refer
to Section 4, Troubleshooting.
4. Start the generator set by moving the generator set
master switch to RUN. Test operate the generator
set to verify that the cause of the shutdown has
been corrected.
5. Move
the
generator
set
master
switch
to
OFF/RESET.
6. Reconnect the generator set to the load using the
line circuit breaker or ATS.
7. Move the generator set master switch to the AUTO
position for startup by remote transfer switch or
remote start/stop switch.
Note: The controller's
LED display remains off
until an engine start command is received.
Opening and closing a remote start/stop contact also
resets the controller.
2.3.6
Continuous
Power Mode
The controller is powered by the generator set engine
starting battery. A jumper on the back of the controller
maintains
power
to
the
controller
at
all times.
Controllers are shipped with the jumper connected.
Note: The 8.5 and 12 RES generator sets are equipped
with factory-installed
battery chargers to prevent
battery discharge.
Disconnecting the jumper allows the controller to power
down automatically
48 hours after the generator set
shuts down if the generator set master switch is in the
AUTO position.
A remote start signal (from a transfer
switch or a remote
start/stop
switch connected
to
controller leads 3 and 4) or moving the generator set
master switch to the RUN position turns the controller
back on.
See Section 6.9.3 for instructions
to disconnect the
jumper.