Kohler Industrial Generator Set Operation Manual page 28

10-1000 kw with apm402 controller; decision-makerr 3000 controller
Table of Contents

Advertisement

Factory-Defined Settings List
Description
Engine Functions
Critically high fuel level
(diesel-powered models only) *
ECM communications loss
ECM diagnostics (multiple
inputs) [
ECM diagnostics (multiple
inputs) [
ECM faults (address conflict)
ECM faults (model mismatch)
Engine over speed
Engine start aid active
Engine under speed
Fuel tank leak *
Fuel tank leak *
High battery voltage
High coolant temperature
High coolant temperature
High fuel level (diesel-powered
models only) *
Loss of fuel
Low battery voltage
Low coolant level *
Low coolant temperature
Low cranking voltage
Low engine oil level *
Low engine oil level *
Low fuel level (diesel models) *
Low fuel level (diesel models) *
Low fuel pressure
(gas models) *
Low oil pressure
Low oil pressure
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST--Short Term, LT--Long Term
28
Section 1 Specifications and Features
Controller Display
Alarm
Message
Horn
Fuel Level Critically
On
High
ECM Comm Err
On
Shutdwn
ECM xxxxxx Warning
On
ECM xxxxxx Shutdwn
On
ECM Addr Err
On
Shutdwn
ECM Mismatch
On
Shutdwn
Eng Speed High
On
Shutdwn
Starting Aid Notice
Eng Speed Low
On
Shutdwn
Fuel Leak Warning
On
Fuel Leak Shutdwn
On
Battery High Warning
On
Coolnt Temp High
On
Warning
Coolnt Temp High
On
Shutdwn
Fuel Level High
On
Warning
Loss of Fuel
On
Battery Low Warning
On
Coolant Lvl Low
On
Shutdwn
Coolant Temp Low
On
Warning
Lo Crank Vlt Warning
On
Oil Level Low Warning
On
Oil Level Low Shutdwn
On
Fuel Level Low
On
Warning
Fuel Level Low
On
Shutdwn
Fuel Press Low
On
Warning
Oil Press Low Warning
On
Oil Press Low
On
Shutdwn
GenSet
Fault
Write
Mode
Lamp
Access
Always
Warning
Display
Running
Shutdown
SiteTech
Stopped
W
S
W
S
S
S
S
S
A
S
S
A
W
S
W
S
A
W
S
W
S
W
S
A
S
W
W
W
S
W
S
W
W
S
Time
Delay
Range
Default
Range
Setting
Selection
(sec.)
0--100%
95%
0--10
Fixed
0--255
0
105--120%
115%
75--95%
85%
110--135%
125%
Fixed
0--10
(0--30
inhibit)
0--10
(0--30
inhibit)
0--100%
90%
0--10
80--105%
100%
Fixed
Fixed
0--10
16_C
Fixed
(0--30
(60_F)
inhibit)
Fixed
60%
Fixed
0--100%
35%
0--10
0--100%
5%
0--10
Fixed
(Fixed
inhibit)
Fixed
(Fixed
inhibit)
TP-6694 7/18
Default
Time
Delay
(sec.)
5
10
10
0
(5 FAA)
(0
inhibit)
0
(0
inhibit)
5
90
5
5
(0
inhibit)
6
10
0
0
(30
inhibit)
5
(30
inhibit)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents