2.7.14 Event Log

Displays up to 1000 stored status, warning, and
shutdown events. After the first 1000 events, each
additional new event replaces the oldest event. See
1.2.4 Controller Fault Diagnostics for a list of possible
events.
Event Log
Event Log ---->

2.7.15 Volt Select

This menu is not available on Decision-Makerr 3000
Controllers with firmware versions before 2.8.22.
This menu allows the user to readily change controller
voltage settings. The volt select feature is typically used
in towable or temporary applications.
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
Note: The volt select menu requires initial activation by
SiteTecht software.
select True to activate the volt select menu.
Note: The generator set output leads require voltage
reconnection if the generator set does not have a
voltage selector switch installed.
With the generator set stopped, go to the Volt Select
menu.
Then push and hold the pushbutton/rotary
selector dial until the voltage selection starts to flash.
Volt selection is now available. Scroll to the desired
voltage and momentarily press the pushbutton/rotary
selector dial to confirm the voltage selection.
62
Section 2 Operation
#####
(Message Text)
(Scroll through up to 1000
max. stored events)
In SiteTecht software,
Volt Select
Volt Select: ---->
###/### V # Ph
120/240 V 1 Ph
120/208 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
120/240 V 3 Ph
TP-6694 7/18