Analog Inputs - Kohler Industrial Generator Set Operation Manual

10-1000 kw with apm402 controller; decision-makerr 3000 controller
Table of Contents

Advertisement

Digital Outputs
AC Sensing Lost
Alternator Protection
Auxiliary Input
Battery Charger Fault
Battery Voltage
Chicago Code Active
Common Fault
Common Warning
Cranking Voltage
ECM Comm Loss
Emergency Stop
Engine Coolant Level
Engine Coolant Temperature
Engine Cooldown Active
Engine Fuel Level
Engine Oil Level
Engine Oil Pressure
Engine Speed
Engine Start Aid Active
Engine Start Delay Active
EPS Supplying Load
Fuel Pressure
Fuel Tank Leak
Generator Frequency Average
Generator Running
Generator True Total Power
Generator Voltage L1--L2
Generator Voltage L2--L3
Generator Voltage L3--L1
Ground Fault
Locked Rotor
NFPA 110 Alarm Active
Not In Auto
Overcrank
Speed Sensor Fault
System Ready
* NFPA 110 Defined Common Alarms
Figure 2-21 Digital Outputs with NFPA 110 Defined Common Alarms

2.7.12 Analog Inputs

Displays the selected programming user-defined
analog notice, warning, and shutdown inputs. These
inputs provide a multitude of choices for configuring
customized auxiliary inputs. See Figure 2-20 for a list of
analog input choices. For descriptions of the inputs
listed refer to the following:
2.4.5 System Fault Warning Lamp with Digital
D
Displays
2.4.6 System Fault Shutdown Lamp with Digital
D
Displays
2.4.7 Status and Notice Digital Displays
D
60
Section 2 Operation
Low
Warning
Notice
Warning
X
X
X*
X*
X
X
X
X
X*
X
X*
X
X*
X
X
X
X*
X
X
X
X
X*
X
X
Critical
High
High
Warning
Warning
Shutdown
X
X
X
X*
X
X
X*
X*
X*
X
X
X*
There is an optional 2 input/5 output (I/O) module board
available that can provide two additional analog (or
digital) inputs.
The displays for analog inputs appear as shown below
and have an acceptable operating range (0--5 VDC).
The analog input selection typically requires entering
four values—low warning, high warning, low shutdown,
and high shutdown.
AIn A1 (analog input A1) standard
D
(reserved and not user programmable)
AIn A2 (analog input A2) standard
D
(Identified as A1 on SiteTecht software)
No Signal
Low
High
Shutdown
Shutdown
Shutdown
X*
X*
X*
X
X*
X*
X
X
X
X
X
TP-6694 7/18
X*
X*
X
X
X
X
X