Terminal Jumper; Communication Ports; Fuses - Kohler Industrial Generator Set Operation Manual

10-1000 kw with apm402 controller; decision-makerr 3000 controller
Table of Contents

Advertisement

10
9
8
6
7
1. (4) push-on terminal connectors
2. TB2 4-position terminal block
3. TB3 6-position terminal block
4. P2 6-pin connector
5. P1 24-pin connector
6. TB1 6-position terminal block
7. P22 3-pin connector
8. P30 jumper (Wound Field or Fast Response)
9. P23 8-pin connector (RJ45)
10. P21 6-pin connector (for RS-485 communication)
Figure 1-5 Main Circuit Board Connectors
P21 (6-Pin) Connector for (RS-485) connection of
optional RSA or Modbusr communication.
P22 (3-Pin) Connector for engine ECM. Alternate CAN
connection.
P23 (8-Pin) Connector (RJ45) for optional input/output
(I/O) module circuit board.
Refer to Section 6.2, Accessory Connections for
specific connections of the following terminal block
connections.
TB1 (6-Position) Terminal Block for analog and digital
inputs.
TB2 (4-Position) Terminal Block for K1 relay outputs.
TB3 (6-Position) Terminal Block for E-stop, remote
start contacts, and aux. input connections.
1.2.7

Terminal Jumper

A circuit board P30 jumper is set based on alternator
type—Wound
Field
Fast Response (less than 350 kW). The jumper is
factory set and needs no further adjustment.
Figure 1-5 for location of the P30 jumper.
Modbusr is a registered trademark of Schneider Electric.
26
Section 1 Specifications and Features
GM64345-1-A
5
(300
kW
and
larger)
1.2.8

Communication Ports

The main logic circuit board contains a single mini USB
1
communication port for PC connections, see Figure 1-6.
For Modbusr communication using RS-485, see
Figure 1-5 (P21). Refer to the List of Related Materials
in the Introduction for corresponding SiteTecht
2
software and/or communication installation information.
3
4
1. Mini USB connection
Figure 1-6 Communication Port
1.2.9

Fuses

AC Circuit Fuses (TB5). Fuses are located inside the
generator set control box. See Figure 1-7
1.5-Amp (V7) fuse protects L1 sensing input to
D
interconnection circuit board.
1.5-Amp (V8) fuse protects L2 sensing input to
D
interconnection circuit board.
1.5-Amp (V9) fuse protects L3 sensing input to
D
interconnection circuit board.
DC Circuit Fuses are located on the controller circuit
board. See Figure 1-8.
1-Amp (F1) auto-resettable, fuse protects the
D
controller circuits.
1-Amp (F2) auto-resettable fuse protects the
D
controller circuits.
12-Amp (F3) non-replaceable fuse protects the
D
engine/starting circuitry and accessories.
or
See
GM65741-
1
TP-6694 7/18