Connection to a PC by the NT Link
2-6-3

PC Switch Settings

38
when the NT11S and PC are connected to each other, set the conditions at the PC
CPU so as to enable the NT link communications.
S C-series C200HS, CQM1
Set the operating conditions to the PC system setting area when a C200HS or
CQM1 CPU is connected to the NT11S. The PC system setting area (data
memory) can be directly accessed from the peripheral tool (LSS etc.).
The following describes the switch settings so as to enable the PC system set-
tings. For the details of the operation with the PC system setting area, refer to the
"SYSMAC CQM1-CPM1 Programming Manual" (W228-E1-j).
[Switch setting] (CQM1 only)
[PC system setting area settings]
Write settings to the PC system setting area (data memory).
Channel No.
DM6645
S RS-232C port communication conditions (DIP SW5)
Set SW5 to "OFF" to effect the existing settings of the
PC system setting area.
Writing value
4000
Section 2-6
Settings
NT link is used.