Faceplate Display Information; Table 8 C300 Controller Faceplate Display Indications - Honeywell C300 User Manual

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

LED Indication
¼ second
AND faceplate display is blank.
( i.e. ¼ sec ON, ¼
sec. OFF)
OFF
AND faceplate display is frozen
(a blank or frozen
or blank.
display)

Faceplate display information

The four-character display on the C300 faceplate shows a variety of information
depending upon the controller state and status:
During controller power-up, the display indicates the controller's Power-On Self Test
execution and software version.
The controller's operating state the display shows in a rotating display the FTE
Device Index, CEE state, and soft failures (such as redundancy, communications, or
diagnostic faults).
The controller's redundancy role and synchronization status.
Fault codes when the controller ceases normal operation due to a major fault.
Table 8 includes a listing and descriptions of the various indications of the C300
Controller display.

Table 8 C300 Controller faceplate display indications

C300 Faceplate
Display
(####)
Communication Failure - No effect on controller state,
See Note 1
shown on Control Builder forms and Station displays.
Tnnn
POST test number - Transient state, No CDA.
-BP-
Controller in BOOTP mode waiting for IP address from
BOOTP Server - Transient state, No CDA.
-TS-
Controller is attempting connection to configured time
R500
April 2017
Status/Description
Indicates...
Series 8 C300 Controller User's Guide
Honeywell
7. C300 Controller Operation
7.2. C300 faceplate indicators/displays
Indicates: Hardware Watchdog Timer
expired or other major fault.
Indicates: Fault (Hardware watchdog
timeout or hardware failure)
(PCMSTATE)
Control Builder
OFFNET
N/A
BOOTING
BOOTING
C300 State
shown on
Station and
displays
181

Hide quick links:

Advertisement

Table of Contents
loading