3. C300 Controller Installation and Upgrades

3.2. C300 Controller installation

ESD HAZARD
Electrostatic discharge can damage integrated circuits or semiconductors if
you touch connector pins or tracks on a printed wiring board. Follow these
guidelines when you handle any electronic component:
Touch a grounded object to discharge static potential
Wear an approved wrist-strap grounding device
Do not touch the wire connector or connector pins
Do not touch circuit components inside a component
If available, use a static safe workstation
When not in use, keep the component in its static shield box or bag
WARNING
Unless the location is known to be non-hazardous, do not connect or
disconnect cables while the control system is powered.

Series 8 control hardware installation requirements

Refer to Planning Your Series 8 Control System section in the Control Hardware
Planning Guide for details.
3.2
C300 Controller installation

C300 Controller assembly

The C300 Controller consists of an Input/Output Terminal Assembly (IOTA) board and
the controller module which is housed within a plastic cover and is mounted on the IOTA
board. The Controller assembly is installed in a control cabinet on vertically-mounted
channels specifically for Series 8 control hardware. The following figure shows the
features of the C300 Controller IOTA board.