Step
4
Once the load completes and the dialog
box closes, click the Monitoring tab.
5
Refer to the section
to set the C300 to its Run state.
6
Repeat this procedure for other control
components as required.

Loading IOMs and CMs

Follow the initial load order guidelines in Table 3 to load these additional control
strategy components.
Before you load IOMs, make sure that the I/O Modules are installed and capable of
communicating with the Server, otherwise errors will result. To Load IOMs, you
select the associated CEEC300 block and perform a
load check boxes for any CMs are not checked in the Load Dialog. You can also
load IOMs individually using the Load command; just be sure that the associated
IOLINK block is loaded first.
Load CMs and SCMs after other control strategy components are loaded. To
Load CMs and SCMs, select the associated CEEC300 block and perform a
Contents.' Be sure only load check boxes for CMs and SCMs are checked.
Refer to the Control Building User's Guide for more details about these procedures.
R500
April 2017
Action
Activating the CEE

Series 8 C300 Controller User's Guide

Honeywell
6. Load C300 Controller Configuration
6.4. Load With Contents command
Result
CEE icon now appears in Monitoring tab.
The default state for a loaded CEE is
inactive/idle or color code blue.
CEE icon turns green when active.
'Load with
Contents.' Be sure
'Load with
169