Download Print this page

Specifications; Ordering Information - Honeywell V9055A Manual

Modulating fluid power gas valve actuator

Advertisement

V9055A,D
SPECIFICATIONS • ORDERING INFORMATION
MODELS:
V9055A: Modulating Fluid Power Gas Valve Actuator.
V9055D: Modulating Fluid Power Gas Valve Actuator
with proof-of-closure switch.
PRESSURE RATINGS OF ACTUATOR-VALVE COMBINATIONS:
Valve
V5055B
3/4-3 in.
V5055B
4 in.
V5055A,C
3/4-3 in.
V5055A,C
4 in.
V5055D,E
3/4-1-1/2 in.
V5055D,E
2, 2-1/2, 3 in.
a
The low-fire flow of the V5055A,C,D and E Valves will differ from those of the V5055B. Check the valve flow curves in
form 70-8311 and match the low-fire adjustment to the burner design and application.
ELECTRICAL RATINGS:
Voltage/
Frequency
Watts
120/60
60
100-50/60
57/46
220/50
68
240/50
88
When purchasing replacement and modernization products from your wholesaler or your distributor, refer to the TRADELINE
price sheets for complete ordering number. Specify —
1. Order number
2. Voltage and frequency
3. Standard opening time
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422 (612) 954-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International sales and
service office in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2311—6
a
V9055
5 psi [35 kPa] diff.; 15 psi [105 kPa] closeoff
3 psi [21 kPa] diff.; 15 psi [105 kPa] closeoff
5 psi [35 kPa] diff.; 15 psi [105 kPa] closeoff
3 psi [21 kPa] diff.; 15 psi [105 kPa] closeoff
5 psi [35 kPa] diff.; 75 psi [525 kPa] closeoff
5 psi [35 kPa] diff.; 45 psi [315 kPa] closeoff
Opening
Holding
VA
Watts
122
20
100/81
25/20
36/31
141
20
194
19
LOW-FIRE ADJUSTMENT: 0.14 inch to 0.65 inch (with
respect to V5055B Valve) valve stem travel. Refer to
form 70-8311 for valve flow (capacity) curves.
Actuator
5 psi [35 kPa] diff.; 15 psi [105 kPa] closeoff
3 psi [21 kPa] diff.; 15 psi [105 kPa] closeoff
5 psi [35 kPa] diff.; 75 psi [525 kPa] closeoff
5 psi [35 kPa] diff.; 45 psi [315 kPa] closeoff
AUXILIARY AND PROOF-OF-CLOSURE SWITCH
RATINGS: 1/2 hp
VA
Full Load
32
Locked Rotor
a
Maximum total connected power to both switches (if
used) is 1800 VA.
32
36

Ordering Information

4. Accessories, if required
5. NEMA 4 enclosure, if needed
2

Specifications

a
V9055 D
(use with V5055C,E)
a
.
120V
9.8A
58.8A
240V
4.9A
29.4A
®
catalog or