5. C300 Configuration Form Reference
5.1. C300 Controller Block
Plain Text
Disable Battery
Alarm and Soft Fail
GPS Time Source
Enabled
Temperature High
Alarm (degC)
CPU Free Low Alarm
(%)
CPU Free Low Low
Alarm (%)
Simulation Node Configuration
Load to simulation
Environment
Host IP Address
Host Name
Simulation Node Operation
90
Parameter Name
DISABLEBATTERYALA
RM
GPSENABLE
(Currently not used)
OVERTEMPTHLD
CPULOLM
CPULOLOLM
SIMTARGET
HOSTIPPRI
HOSTNAMEPRI
Series 8 C300 Controller User's Guide
Honeywell
User
Configurable
Project only
Allows you to enable or
disable the battery-related
soft failures and events to
be reported.
When this parameter is
checked, battery-related
soft failures and events
are not reported when a
battery is not connected.
When this parameter is
unchecked, battery-related
soft failures and events
are reported.
Yes
Allows you to select GPS
as TIMESOURCE for time
synchronization.
Yes
Set threshold value for
module's temperature high
alarm.
Yes
Allows user to set CPU
Free Low Capacity alarm
limit in percent.
Fixed CPU Free Low Low
No
Capacity alarm limit in
percent.
Yes
Enables load to simulation
environment.
No
Indicates the IP address
for the node hosting the
simulation program.
No
Specifies the network
name for the node hosting
the simulation program.