Tracer Sc Bas Integration; Bas Unit Control - Trane Tracer UC600 Integration Manual

For packaged outdoor air unit
Table of Contents

Advertisement

Using this method, the Device ID is limited to the range of 0 to 127. When there is a need to set
the Device ID to a value greater than 127, software configuration must be used.
shows the setup page that is available in Tracer TU. A very similar page is available in the
BACnet Setup Tool.
To set the Device ID using the software configuration method:
1. Navigate to the Device ID section of the Protocol frame of the page.
2. Enable the Use Software Device ID feature by checking the selection box.
3. Enter the desired value for the BACnet Device ID in the text box.
4. Save the configuration change to the device.
5. Cycle power to the device to have the new value take effect.
N N o o t t e e : : When the software method is enabled the hardware method is automatically disabled.
Figure 3. Example showing rotary dial settings and the BACnet device ID

Tracer SC BAS Integration

When Tracer SC is the BAS, the integration technician is not required to manually configure the
Device ID of the UC600. The Tracer SC will do this as part of the site discovery and installation
process.
Tracer SC will perform the following steps:
1. Enable the Use Software Device ID feature.
2. Calculate a unique BACnet Device ID value, based on Tracer SC Device ID, MS/TP link
3. Send the BACnet Device ID value to the device.

BAS Unit Control

The UC600 gets controlled by the BAS by changing values of point and placing points in or out of
service.
BAS-SVP18D-EN
number, and MAC address of the unit controller.
C C o o n n f f i i g g u u r r i i n n g g t t h h e e U U C C 6 6 0 0 0 0
Figure 3, p. 11
11

Advertisement

Table of Contents
loading

Table of Contents