11. Select OK to acknowledge.

7.1.4 Correct Input at Sensor 1 / 2 Calibration High Point

1. Select the S 1 / 2 Cal Hi Corrects button. This message appears.
1. Check the device is not in write protect mode and press OK
2. Enter calibration date (MM/DD/YY), OK
3. Enter calibration Time (Hour), OK. Entre calibration time (minute), OK
4. Apply input on Sensor 1.
Page 84
STT700 Series HART/DE Option User's Manual
Revision 1