Honeywell SmartLine STT700 HART User Manual page 42

Stt700 series hart/de option
Hide thumbs Also See for SmartLine STT700 HART:
Table of Contents

Advertisement

Online/Device Setup/Basic
Configuration/
4-20mA Outputs
Summary
Page 42
PV Damp
Poll Address
Loop Current Mode
NAMUR Option
PV % range
PV LTL
PV UTL
Displays the current values under Basic Configuration Menu for all of
the pertinent operating parameters listed in this table. Parameters are
not configurable in this menu
STT700 Series HART/DE Option User's Manual
Enter a value for damping of the device
output. Entries may be any value from 0.00
to 102.00 seconds.
The following output-related values and
operations are available in this menu:
Poll Address: Select HART short address 0
to 63.
Loop current mode: Select the Loop
Current Mode configuration:
"Enable": enables loop current mode
(analog output will operate as a 4 to 20 mA
signal consistent with the transmitter
output)
"Disable": disables loop current mode
(analog output will be fixed at 4 mA)
Select from the following:
Namur Selection: select to enable or
disable the Namur option for the output.
(Refer to the PV Ranges/Limits chart) for
effect on output signal.
Namur Level: Displays a diagram of the
operating range and failsafe range of the
Analog output for Normal and Namur
configurations.
Displays the current value of transmitter
Output in %
Lower Transducer Limits
Upper Transducer Limits