Advertisement

5. Adjust the PV input Temperature to the exact value of the Sensor1 high calibration point
entered. Select the OK button.
6. Observe the input temperature at the applied value; when it is stable, select the OK button.
7. A screen appears Remove applied input on sensor 1.
STT700 Series HART/DE Option User's Manual
Revision 1
Page 85