Honeywell SmartLine STT700 HART User Manual page 68

Stt700 series hart/de option
Hide thumbs Also See for SmartLine STT700 HART:
Table of Contents

Advertisement

6. Select the Set button. You will be prompted to confirm that you want to put the transmitter in
output mode.
7. Select Yes, and note the output current at 0%, 100% or the other value established in the
previous step. With the transmitter in analog mode, you can observe the output on an
externally connected meter or on a display. In DE mode, the output can be observed on the
display or on the monitor display of the MC Toolkit.
8. To view the Monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A confirmation prompt will be displayed for you to verify that you want
to change pages. Select Yes.